Certification
6.2 EMC and Environmental Type Tests
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
•
NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX1400 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
± 8 kV
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
± 4 kV @ 2.5 kHz, 5 kHz
Note
DC Power Ports
± 4 kV @ 2.5 kHz, 5 kHz
AC Power Ports
± 4 kV
IEC 61000-4-4
Burst (Fast Transient)
Earth Ground Ports
± 4 kV @ 2.5 kHz, 5 kHz
4
Signal Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
DC Power Ports
± 2 kV Line-to-Earth
± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge Immunity
AC Power Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced (Conducted) RFI
Earth Ground Ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure Ports
100 A/m Continuous
1000 A/m for 1 s
5
IEC 61000-4-9
Pulse Magnetic Field
Enclosure Ports
300 A/m
4
IEC 61000-4-11
Voltage Dips & Interrupts
AC Power Ports
30% for 0.5 Cycles
60% for 5 Cycles
100% for 250 Cycles
Signal Ports
IEC 61000-4-16
Mains Frequency Voltage
DC Power Ports
30 V Continuous
300 V for 1s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
60
RUGGEDCOM RX1400
Installation Manual, 01/2021, C79000-G8976-1103-17