Installing the Device
2.4 Connecting the Failsafe Alarm Relay
2. Place the device against the panel and align the adapters with the mounting
holes.
2
1
2
1
1
Screw
2
Panel Adaptor
Figure 2.3
Panel Mounting
3. Secure the adapters to the panel with #6-32 screws.
2.4
Connecting the Failsafe Alarm Relay
The failsafe relay can be configured to latch based on alarm conditions. The NO
(Normally Open) contact is closed when the unit is powered and there are no active
alarms. If the device is not powered or if an active alarm is configured, the relay
opens the NO contact and closes the NC (Normally Closed) contact.
Note
Control of the failsafe relay output is configurable through RUGGEDCOM
RUGGEDCOM RS940GF . One common application for this relay is to signal an
alarm if a power failure occurs. For more information, refer to the
RUGGEDCOM
RUGGEDCOM RS940GF User Guide
for the RUGGEDCOM RS940GF.
The following shows the proper relay connections.