Technical Specifications
5
This section provides important technical specifications related to the device.
5.1
Power Supply Specifications
Note
When determining cable lengths, make sure the minimum input voltage for the pow-
er supply is provided at the power source.
Hazardous Environments
Input Range
Power Sup-
ply Type
Minimum
Maximum
Internal
Fuse Rating
Isolation
Maximum
Power Con-
125 VDC
250 VDC
3.15 A(T)
4 kVAC
10 W
HI
100 VAC
240 VAC
3.15 A(T)
4 kVAC
10 W
24
12 VDC
24 VDC
3.15 A(T)
1.5 kVDC
10 W
48
37 VDC
72 VDC
3.15 A(T)
1.5 kVDC
10 W
(T) denotes time-delay fuse.
Power consumption varies based on configuration.
Non-Hazardous Environments
Input Voltage
Power Sup-
ply Type
Minimum
Maximum
Internal
Fuse Rating
Isolation
Maximum
Power Con-
sumption
88 VDC
300 VDC
3.15 A(T)
4 kVAC
10 W
HI
85 VAC
264 VAC
3.15 A(T)
5.5 kVDC
10 W
24
10 VDC
36 VDC
3.15 A(T)
1.5 kVDC
10 W
48
37 VDC
72 VDC
3.15 A(T)
1.5 kVDC
10 W
(T) denotes time-delay fuse.
Power consumption may vary based on configuration.
RUGGEDCOM RS930W
Installation Manual, 02/2020, C79000-G8976-1035-07
31