Connecting
3.1 Terminal assignment
PDC1000(F)
20
Equipment Manual, 02/2020, A5E48775040-AA
Interfaces, cable lengths and cable types
The following cable lengths and cable types are permitted for the interfaces.
Table 3- 1
Wiring rules for the interfaces
Plug connector Function
Maximum cable length
Cable type
Cable cross-section
X100
Functional ground
0.1 m
Grounding strap
≥
4 mm
2
X2050
PROFINET Port 1
100 m
Shielded cable, 2 x
twisted pair, Cat 5
-
X2060
PROFINET Port 2
100 m
Shielded cable, 2 x
twisted pair, Cat 5
-
X4050
Incremental encoder
signals and supply
10 m
Shielded
For differential wiring,
one twisted pair per
signal pair
Solid and stranded sup-
ply cable:
AWG*: 22 to 16 or
0.34 mm
2
to 1.5 mm
2
Hall sensor signals and
supply
10 m
Shielded
Encoder and Hall inter-
face with "All-in-one"
plug-in cable
10 m
Shielded in "All-in-one" plug-in cable
X4060
I/O, inputs and outputs 20 m
•
< 2 m unshielded
•
≥
2 m shielded
Solid and stranded sup-
ply cable:
AWG*: 22 to 16 or
0.34 mm
2
to 1.5 mm
2
For through-wiring for
maximum permissible
terminal currents, use
AWG* 16 or 1.5 mm
2
.
Supply of inputs/outputs 20 m
•
< 2 m unshielded
•
≥
2 m shielded
X5050
Power supply of power
unit (4L+, 4M)
20 m
•
< 2 m unshielded
•
≥
2 m shielded
Solid and stranded sup-
ply cable:
AWG*: 20 to 10 or
0.5 mm
2
to 4 mm
2
Use AWG* 10 or 4 mm
2
for the recommended
circuit breaker.
X5051
Connection of external
braking resistor (4R+,
4R-)
2 m
Unshielded
Solid and stranded sup-
ply cable:
AWG*: 18 to 16 or
1.0 mm
2
to 1.5 mm
2
X5055
Motor phases
10 m
Shielded
Solid and stranded sup-
ply cable:
AWG*: 18 to 10 or
1.0 mm
2
to 4 mm
2
Motor phases with "All-
in-one" plug-in cable
10 m
Shielded in "All-in-one" plug-in cable