Setting the KP8 and KP8F
6.5 Setting KP8F - STEP 7
KP8, KP8F
66
Operating Instructions, 10/2010, A5E03284305-01
6.
In the list, select:
– Not activated
"Not activated" is the default entry.
– 1oo2 (2v2)-evaluation, EMERGENCY STOP
– 1oo1 (1v1)-evaluation, single-channel
The selection is based on the connection corresponding with chapter "Connect KP8F -
Note
Make sure that the sensor is monitored corresponding with its connection.
7.
Click "OK".
The entries are saved. The dialog box closes.
8.
Open the "PROFIsafe" tab.
If no access rights exist, the following dialog box will be shown.
9.
Enter the password that was assigned when the safety program was created in
Distributed Safety.
10.
Click "OK".
The dialog box closes.
11.
If necessary, change the "F_Dest_Add" parameter.
To do this, use the "Change value" button. Assign a network and station-wide unique
address.
12.
Change the monitoring time "F_WD_Time" if needed.
13.
Click "OK".
The entries are saved. The dialog box closes.
Result
The HMI device will now respond in operation according to the new setting. The switch
states of the digital inputs of the HMI device are stored in the specified address area of the
controller.