Planning the use
3.7 Requirements for fail-safe operation
KP8, KP8F
40
Operating Instructions, 10/2010, A5E03284305-01
Signal duration
In order to assure accurate detection of the sensor signal by the HMI device, you must
ensure that the minimum duration for the sensor signal is adhered to. Refer to chapter
"Technical specifications (Page 84) ". The minimum duration is ensured by the usage of
push-to-lock emergency stop buttons.
3.7.3
Cables
The cables used must meet the following requirements:
● The unique assignment of terminals to sensors must be ensured.
● Cables laid outside of the switching cabinet must be laid separately in accordance with
the relevant standards.
Use stable pipes or cable channels in order to avoid short circuits and cross-circuits.
Note
With the connection of an emergency stop button to the fail-safe channels of the HMI
device, the line lengths corresponding with chapter "Technical specifications (Page 84)"
must be complied with.