Planning the use
3.3 Ambient conditions for operation
KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01
31
Use with additional protective measures
You may only use the HMI device at the following locations with additional protective
measures:
● In locations with a high degree of ionizing radiation
● In locations with difficult operating conditions, for example due to:
– Corrosive vapors, gases, oils or chemicals
– Electrical or magnetic fields of high intensity
● In systems that require special monitoring, for example:
– Elevators
– Systems in especially hazardous rooms
Damping shock and vibration
If the HMI device is subjected to strong shocks or vibrations - as specified in the following
table - you must take appropriate measures to reduce amplitudes or acceleration. In such
situations, use vibration damping or vibration absorber systems for the HMI device and
accessories.
Testing mechanical ambient conditions
In the following table contains tests that were checked on the HMI device in regards to the
ambient conditions for operation.
Test
Physical variable
Value
Vibration
1 octave/min
10 cycles per axis
5 to 8.4 Hz:
Deflection 3.5 mm
Vibrations
IEC 60068-2-6:2007
Test Fc
Frequency band
8.4 to 150 Hz
Vibration acceleration 9.8 m/s
Shock form
Half sine
Acceleration
150 ms
-2
Duration
11 ms
Shock
IEC 60068-2-27:2008
Test Ea
Number of shocks
3 per axis
Case
DIN EN 60068-2-31:2009
Test Ec
Fall height
0.3 m, five times