Technical specifications
5.6 Classification of environmental conditions
Comfort Panels INOX, ITC INOX
46
Compact Operating Instructions, 08/2022, A5E33472156-AP
Ambient temperature during operation
Type of condition
Mounting position
Permissible range
Temperature,
Landscape mounting
Vertical
0 °C to 50 °C
1
inclined, incline max. 35°
0 °C to 40 °C
Temperature,
Portrait mounting
Vertical
0 °C to 40 °C
inclined, incline max. 35°
0 °C to 35 °C
1
TP1900 Comfort INOX and ITC1900 INOX: 0 °C to 45 °C
2
No pressure difference inside and outside of the enclosure/control cabinet permitted
Humidity and atmospheric pressure during operation
Test
Value, range
Comment
Humidity
•
TP700/TP900 Comfort INOX
10% to 90%
No condensation
•
TP1200/1500 Comfort INOX
•
TP1200 Comfort INOX LF
10% to 80%
No condensation
•
TP1900 Comfort INOX,
ITC1900 INOX
10% to 70%
No condensation
Atmospheric pressure
1
1140 hPa to 795 h
Pa
Corresponds to an altitude of -1000 m to
2000 m
1
No pressure difference inside and outside of the enclosure/control cabinet permitted
Observe the Notes on use (Page 12).
In addition, observe the climate diagram in the following section and the information on the
extended inclination and ambient temperature range, see section "Selecting a mounting
position (Page 14)".
Note
System components connected to the HMI device, such as the power supply, must also be
suitable for operation under the corresponding rated conditions.