Installing and connecting the device
3.4 Connecting the device
Industrial Thin Client ITC1200, ITC1500, ITC1900, ITC2200
28
Operating Instructions, 04/2013, A5E03474888-02
Wiring diagram
①
Ground connection on the device, example
②
Equipotential bonding conductor cross-section: min. 4 mm
2
③
Control cabinet
④
Equipotential bonding conductor cross-section: min. 16 mm
2
⑤
Ground connection
⑥
Cable clip
⑦
Equipotential bonding rail
⑧
Parallel routing of the equipotential bonding conductor and data cable
NOTICE
Damage to the interface modules possible
Cable shielding is not suitable for equipotential bonding.
Use only the prescribed equipotential bonding conductors. The equipotential bonding
conductor
④
must not be less than 16 mm². The interface modules may otherwise be
damaged or destroyed.