Technical specifications
9.4 Technical specifications
Industrial Thin Client ITC1200, ITC1500, ITC1900, ITC2200
114
Operating Instructions, 04/2013, A5E03474888-02
Testing mechanical ambient conditions
The following table provides information on the type and scope of tests for mechanical
ambient conditions.
Tested for
Test standard
Comments
Type of vibration:
Frequency cycles at a rate of change of 1
octave/minute.
5 Hz ≤ f ≤ 8.4 Hz, constant amplitude 0.075 mm
8.4 Hz ≤ f ≤ 150 Hz, constant acceleration 1 g
1
Vibrations
Vibration test in accordance
with IEC 60068, part 2–6
(sinusoidal)
Vibration duration:
10 frequency cycles per axis in each of the three
mutually vertical axes
Type of shock: Half-sine
Severity of shock:
Peak value 15 g, duration 11 ms
Shock
Shock test in accordance
with IEC 60068, Part 2 –27
Direction of shock:
3 shocks in ± direction of axis in each of the
three axes vertical to each other
Climatic ambient conditions
The following table shows the climatic ambient conditions for operation of the device.
Ambient conditions
Permitted range
Comments
Temperature:
Vertical mounting
Mounting at an angle
From 0 to 50 °C (horizontal)
1
From 0 to 40 °C (horizontal)
Slope angle max. 35°
Relative humidity
10 to 90%, without condensation
Atmospheric pressure
1 080 to 795 hPa
Corresponds to an elevation
of -1000 m to 2000 m
SO
2
: < 0.5 vpm;
Relative humidity < 60%, no
condensation
Test: 10 cm
3
/m
3
; 10 days
Pollutant concentration
H
2
S: < 0.1 vpm;
Relative humidity < 60%, no
condensation
Test: 1 cm
3
/m
3
; 10 days
1
ITC1900 and ITC2200: From 0 to 45° C