C-11
Communications Processor CP 541
EWA 4NEB 812 6188-02
If you configure a DP connection, at least one of the two parameters NWI or
NWO must be
0.
If you have configured a DP connection in an S5-115F, you cannot addition-
ally install a non-safety-related PLC-PLC connection.
Reason: In both connections, the S5-115F uses node address 0 (SINEC L1
master).
The following example shows the contents of block DPS.
For the exchange of data on the DP connection, 16 words of input data and
16 words of output data are allowed for. The DP watchdog has been set to
500 ms.
0:
KS =’DPS:
’;
12:
KS =’NWI 16 NWO 16
’;
24:
KS =’DPWD 50
’;
DP Connection
Special Note for
S5-115F
Example of DPS
Parameters of DB1