6-7
Communications Processor CP 541
EWA 4NEB 812 6188-02
Table 6-4
DB1 Error Codes, continued
Error Code
Remedy
Meaning
In DL
Remedy
Meaning
In DR
04
H
XX
H
1
Parameter syntax error
Verify the structure of parameters in the speci-
fied block and fully specify all parameters.
05
H
XX
H
1
Argument syntax error or over-
range/underrange
Observe the structure of individual parameters
and enter the right value.
06
H
XX
H
1
Overrange/underrange in an ar-
gument
Observe the value range of individual parame-
ters and enter the right value.
07
H
XX
H
1
Parameter combination not al-
lowed, the values in various pa-
rameters are mutually exclusive.
Check the values in parameters TLN, STA,
HSA, SET, SDT 1, L1M, PRI, NWI and NWO.
Enter the right values.
17
H
XX
H
1
L2 interface not operational
Check the parameters for SINEC L2.
21
H
XX
H
1
TLN beyond permissible value
range (1 to 30)
Specify the right station number of the CP 541.
22
H
XX
H
1
TLN of an active station is
greater than highest station num-
ber HSA.
Check SINEC L2. HSA must be the same for all
stations.
23
H
XX
H
1
A connection to the own station
number has been established.
Modify the user program of the connected PLC.
26
H
XX
H
1
The value of SET must be
greater than the value of SDT 1.
The specification is: SET>(SDT 1 – 35)/2.
Check the values of SET and SDT 1 and enter
the right values.
29
H
XX
H
1
An L2 basic parameter is mis-
sing.
Check whether all L2 basic parameters have
been correctly entered.
You must specify the following basic parame-
ters:
STA = AKT: TLN, STA, BDR, HSA, TRT, SET,
ST, SDT 1 and SDT 2
STA = PAS: TLN, STA, BDR, ST and SDT 1
Enter the missing parameters.
30
H
XX
H
1
Frame designator SL2 is present
more than once.
Delete the excessive SL2 frame.
31
H
XX
H
1
The value of SDT 2 is too low in
relation to SET.
The specification is: SDT 2
(35+2xSET).
Enter the right values for SDT 2 and SET.
32
H
XX
H
1
The value of SDT 2 is too great
in relation to ST.
The specification is: (ST
15)
SDT 2. Enter
the right values for SDT 2 and ST.
1
DR specifies the error location for most error messages. The following error locations are possible:
–
04
H
: error in SL2 block
–
14
H
: error in COM block
–
15
H
: error in DPS block
Diagnostics and Error Handling