H-13
Communications Processor CP 541
EWA 4NEB 812 6188-02
Given in the following are the data blocks (DBs), function blocks (FBs) and
organization blocks (OBs) for station 11 (S5-95F).
DB1 in CP 541
DB1
0:
KS =’DB1 SL2: TLN 11 STQ AKT ’;
12:
KS =’ BDR 500 HSQ 30 ’;
24:
KS =’ TRT 30000 ’;
36:
KS =’ SET 80 ST 1000 ’;
48:
KS =’ SDT 1 80 SDT 2 360 ;’;
60:
KS =’#DPS: NWO 16 NWI 16 ’;
72:
KS =’ DPWD 50 ;#’;
84:
KS =’#COM: L1F 0 POL 10 ’;
96:
KS =’ BSAP 52 UPDL 10 ’;
108:
KS =’ PRI ......... ;#’;
120:
KS =’ END ’;
132:
Parameter assignment with COM 95F
Parameters for the operating system
User program signature (CRC checksum):
0
System identification number
(0..255): 0
Interval for OB 13
(0..65535):
80 * 10ms
DB area with constant contents
(Y 2..251/N): Yes 2..251
Maximum PLC cycle time
(10..255): 25 * 10ms
PLC cycle time statistic
(Y/N): No
DB no. for operator action in F operation(J 2..251/N):No
T’mission of error DB via SINEC L1 part-PLC B
(Y/N): No
T’mission of error DB via CP 521
(Y/N): No
Parameter assignment for SINEC L1 with 95F PLC
PG bus number
(Y 1..30/N):
No
SINEC L1 at part-PLC A
(Y/N) : No
SINEC L1 at part-PLC B
(Y/N) : Yes
Slave number
(1..30):
11
Station 11
DB1 in CP 541
COM 95F
Program Examples