A-2
Communications Processor CP 541
EWA 4NEB 812 6188-02
Climatic environmental conditions
to IEC 1131-2
Temperature
Operation
Horizontal installation
Vertical installation
0 ... + 60
°
C
0 ... + 40
°
C
Storage/transportation
– 40 ... + 70
°
C
Temperature change
Operating
3 K/h max.
Non-operating
1 K/min max.
Relative humidity
to DIN 40040
15 ... 95 %
No condensation
Atmospheric pressure
Operating
795 ... 1080 hPa
Non-operating
660 ... 1080 hPa
Pollutants
SO
2
0.5 ppm
relative humidity
60%
no condensation
H
2
S
0.5 ppm
relative humidity
60%
no condensation
Degree of protection to IEC 529
Construction
IP 20
Class
I to IEC 536
Mechanical environmental conditions
Vibrations to IEC 68-2-6
10 Hz
f < 58 Hz
const. amplitude
0.075 mm
58 Hz
f < 150 Hz
const. acceleration 1 g
Repetitive shock tested to VDE 0116
Type of shock
semi-sinusoidal
Shock intensity
15 g peak value
11 ms duration
Number
18 shocks
Drop and topple to IEC 68-2-31
Tested with
drop height 100 mm
Electromagnetic compatibility (EMC)/interference
immunity
Discharge of static electricity to IEC 801-2 Severity 3
Discharge of static
electricity
8 kV discharge in air
Discharge on all parts ac-
cessible to the user in nor-
mal operation
Test voltage
6 kV contact discharge
Electromagnetic fields to IEC 801-3, Severity 3
Field strength
10 V/m
Fast transient noise voltages (burst) to IEC 801-4, Sever-
ity 3
On power supply lines
2 kV
At communication in-
terfaces
2 kV
Spurious emission to EN 55011
Limit class
A
RF test to IEC 801-6, Severity 3
Test voltage
10 V
Frequency range
150 kHz – 80 MHz
IEC/VDE safety specifications
Insulation rating
Between electrically
independent circuits
and circuits connected
to central ground point
to DIN VDE 0160
(05.1988)
or UL 508 CSA 22.2
Nr. 142
Between all circuits
and central ground
point
to DIN VDE 0160
(05.1988)
or UL 508 CSA 22.2
Nr. 142
RFI suppression
to EN 50081-2
industrial application
Test voltage
Rated voltage
V
i
0 ... 50 V DC
Test voltage
500 VDC
Technical Data