LEDs, Connectors, Buttons, CLP
2.4 CLP Slot
SIMATIC CC712
24
Operating Instructions, 05/2019, C79000-G8976-C503-01
Pressing the button
Duration of pressing
the button (seonds)
Function and operation
≥
5 s
Resetting to factory settings
1.
Turn off the power supply.
2.
Switch the power supply on again while pressing the button.
Hold down the button for at least 5 seconds during startup.
Reset is prepared while the "Diagnosis" LED flashes.
3.
Release the button when the LED stops flashing.
While the LED lights up with a green steady light, the gateway performs the reset.
Once reset is complete, the gateway performs a restart and can be reached using the default IP
address set at the factory.
2.4
CLP Slot
The slot for an optional CLP is located on the back of the module.
For information on inserting and removing the CLP, see section Using a CLP (Page 35).
Figure 2-2
Slot for optional CLP on the back of the device