Index
Name Q200
(Description)
Name IEC61850 (Name)
Unit
1P
3W1I
3W3I
3W2I
4W1I
4W3I
220
to
255
H_Vab-y
4
–
PQA2MHAI1$MX$HPPV
$phsABHar(y)
–
PQA2MHAI1$MX
$HPPV
$phsABHar(y)
%
H_Vbc-y
4
–
PQA2MHAI1$MX$HPPV
$phsBCHar(y)
–
PQA2MHAI1$MX
$HPPV
$phsBCHar(y)
%
H_Vca-y
4
–
PQA2MHAI1$MX$HPPV
$phsCAHar(y)
–
PQA2MHAI1$MX
$HPPV
$phsCAHar(y)
%
256
H_Ia-1
(fundamental)
PQA2MHAN1$MX
$HaAmp(1)
PQA2MHAI1$MX$HA$phsAHar(1)
A
257
H_Ib-1
(fundamental)
–
–
PQA2MHAI1$M
X$HA
$phsBHar(1)
–
PQA2MHAI1$MX
$HA$phsBHar(1)
A
258
H_Ic-1
(fundamental)
–
–
PQA2MHAI1$M
X$HA
$phsCHar(1)
–
PQA2MHAI1$MX
$HA$phsCHar(1)
A
259
to
294
H_Ia-x
3
PQA2MHAN1$MX
$HaAmp(x)
PQA2MHAI1$MX$HA$phsAHar(x)
A
H_Ib-x
3
–
–
PQA2MHAI1$M
X$HA
$phsBHar(x)
–
PQA2MHAI1$MX
$HA$phsBHar(x)
A
H_Ic-x
3
–
–
PQA2MHAI1$M
X$HA
$phsCHar(x)
–
PQA2MHAI1$MX
$HA$phsCHar(x)
A
295
H_Pa-1
(fundamental)
PQA2MHAN1$MX
$HaWatt(1)
–
–
–
PQA2MHAI1$MX$HW
$phsAHar(1)
W
296
H_Pb-1
(fundamental)
–
–
–
–
–
PQA2MHAI1$MX
$HW$phsBHar(1)
W
297
H_Pc-1
(fundamental)
–
–
–
–
–
PQA2MHAI1$MX
$HW$phsCHar(1)
W
298
to
333
H_Pa-x
3
PQA2MHAN1$MX
$HaWatt(x)
–
–
–
PQA2MHAI1$MX$HW
$phsAHar(x)
W
H_Pb-x
3
–
–
–
–
–
PQA2MHAI1$MX
$HW$phsBHar(x)
W
H_Pc-x
3
–
–
–
–
–
PQA2MHAI1$MX
$HW$phsCHar(x)
W
Data-Points Mapping
1.6 Harmonics
SICAM, Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97, Manual
19
E50417-H1040-C621-A2, Edition 01.2020