Indications
Table 1-1
Mapping for Indications
Index MQTT
Name Q200 (Description)
Name IEC 61850 (Name)
0
Device OK
LLN0$ST$Health
1
Battery Failure
ZBAT1$ST$BatLo
2
Settings Load
IndGGIO1$ST$Alm2
3
Time Synchronization Error
IndGGIO1$ST$Alm3
4
Limit Violation 1
LimitsGGIO1$ST$Alm1
5
Limit Violation 2
LimitsGGIO1$ST$Alm2
6
Limit Violation 3
LimitsGGIO1$ST$Alm3
7
Limit Violation 4
LimitsGGIO1$ST$Alm4
8
Limit Violation 5
LimitsGGIO1$ST$Alm5
9
Limit Violation 6
LimitsGGIO1$ST$Alm6
10
Limit Violation 7
LimitsGGIO1$ST$Alm7
11
Limit Violation 8
LimitsGGIO1$ST$Alm8
12
Limit Violation 9
LimitsGGIO1$ST$Alm9
13
Limit Violation 10
LimitsGGIO1$ST$Alm10
14
Limit Violation 11
LimitsGGIO1$ST$Alm11
15
Limit Violation 12
LimitsGGIO1$ST$Alm12
16
Limit Violation 13
LimitsGGIO1$ST$Alm13
17
Limit Violation 14
LimitsGGIO1$ST$Alm14
18
Limit Violation 15
LimitsGGIO1$ST$Alm15
19
Limit Violation 16
LimitsGGIO1$ST$Alm16
20
Group Indication 1
GrpIndGGIO1$ST$Alm1
21
Group Indication 2
GrpIndGGIO1$ST$Alm2
22
Group Indication 3
GrpIndGGIO1$ST$Alm3
23
Group Indication 4
GrpIndGGIO1$ST$Alm4
24
Rotation Field Clockwise
IndGGIO1$ST$Alm4
25
SD Card Error
IndGGIO1$ST$Alm5
26
Fault Record
PQA_RDRE1$ST$RcdMade
27
Binary Output 1-S
BinOutGGIO1$ST$Ind1
28
Binary Output 2-S
BinOutGGIO1$ST$Ind2
29
Binary Output 3-S
BinOutGGIO1$ST$Ind3
30
Binary Output 1-R
BinOutGGIO1$ST$Ind4
31
Binary Output 2-R
BinOutGGIO1$ST$Ind5
32
Binary Output 3-R
BinOutGGIO1$ST$Ind6
33
Binary Input 1-S
BinInGGIO1$ST$Ind1
34
Binary Input 2-S
BinInGGIO1$ST$Ind2
35
Binary Input 3-S
BinInGGIO1$ST$Ind3
36
Binary Input 1-R
BinInGGIO1$ST$Ind4
37
Binary Input 2-R
BinInGGIO1$ST$Ind5
38
Binary Input 3-R
BinInGGIO1$ST$Ind6
39
Load profile tariff 1
TOUTariffGGIO1$ST$Alm1
1
40
Load profile tariff 2
TOUTariffGGIO1$ST$Alm2
1
1.2
1
TOUTariffGGIO1 is the IEC 61850 GGIO LN name for TOU indications via the MQTT protocol; not via the IEC61850 protocol.
Data-Points Mapping
1.2 Indications
SICAM, Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97, Manual
11
E50417-H1040-C621-A2, Edition 01.2020