Transient Events
The time stamps of all data points which belong to the same transient event are identical and contain the time
of the start of the transient. A transient duration is not given.
Explanations of the transient events
VarStr:
Start of Event
TrigPh:
Trigger phases
AffPhs:
Affected phases
PeakPh:
Peak phases
MaxVTrs:
Peak voltage
Enumeration values:
1 – Phase A
2 – Phase B
3 – Phase AB
4 – Phase C
5 – Phase AC
6 – Phase BC
7 – Phase ABC
8 – None
9 – Phase ABN
10 – Phase ACN
11 – Phase BCN
12 – Phase ABCN
Table 1-3
Mapping for Transient Events
Index
MQTT
Name Q200
(Description)
Name IEC61850 (Name)
Remark
Unit
51
–
PQA_QVTR1$ST$VarStr
Indication
–
52
–
PQA_QVTR1$ST$TrigPhs
Enumeration
–
53
–
PQA_QVTR1$ST$AffPhs
Enumeration
–
54
–
PQA_QVTR1$ST$PeakPhs
Enumeration
–
55
–
PQA_QVTR1$MX$MaxVTrs
Measured value
V
1.4
Data-Points Mapping
1.4 Transient Events
14
SICAM, Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97, Manual
E50417-H1040-C621-A2, Edition 01.2020