Index
MQTT
Name Q200
(Description)
Name IEC61850 (Name)
Unit
1P
3W1I
3W3I
3W2I
4W1I
4W3I
80
S
–
PQA2MMXU1$MX$TotVA
VA
81
PFa
PQA2MMXN1$MX
$PwrFact
PQA2MMXU1$MX$PF$phsA
–
82
PFb
–
–
PQA2MMXU1$
MX$PF$phsB
–
PQA2MMXU1$MX
$PF$phsB
–
83
PFc
–
–
PQA2MMXU1$
MX$PF$phsC
–
PQA2MMXU1$MX
$PF$phsC
–
84
PF
–
PQA2MMXU1$MX$TotPF
–
85
cos phi (a)
PQA2MMXN1$MX
$ActivePwrFact
PQA2MMXU1$MX$ActivePF$phsA
–
86
cos phi (b)
–
–
PQA2MMXU1$
MX$ActivePF
$phsB
–
PQA2MMXU1$MX
$ActivePF$phsB
–
87
cos phi (c)
–
–
PQA2MMXU1$
MX$ActivePF
$phsC
–
PQA2MMXU1$MX
$ActivePF$phsC
v
88
cos phi
–
PQA2MMXU1$MX$TotActivePF
–
89
Neg. seq. comp. V
–
PQA2MSQI1$MX
$ImbNgV
–
PQA2MSQI1$MX
$ImbNgV
%
90
Neg. seq. comp. I
–
–
PQA2MSQI1$M
X$ImbNgA
–
PQA2MSQI1$MX
$ImbNgA
%
91
Zero seq. comp. V
–
PQA2MSQI1$MX
$ImbZroV
–
PQA2MSQI1$MX
$ImbZroV
%
92
Zero seq. comp. I
–
–
PQA2MSQI1$M
X$ImbZroA
–
PQA2MSQI1$MX
$ImbZroA
%
93
f_10s
PQA2MMXN1$MX
$Hz
PQA2MMXU1$MX$Hz
Hz
94
THDR Va
PQA2MHAN1$MX
$ThdVol
–
–
–
PQA2MHAI1$MX$ThdPhV
$phsA
%
95
THDR Vb
–
–
–
–
–
PQA2MHAI1$MX
$ThdPhV$phsB
%
96
THDR Vc
–
–
–
–
–
PQA2MHAI1$MX
$ThdPhV$phsC
%
97
THDR Vab
–
PQA2MHAI1$MX
$ThdPPV$phsAB
–
PQA2MHAI1$MX
$ThdPPV$phsAB
%
98
THDR Vbc
–
PQA2MHAI1$MX
$ThdPPV$phsBC
–
PQA2MHAI1$MX
$ThdPPV$phsBC
%
99
THDR Vca
–
PQA2MHAI1$MX
$ThdPPV$phsCA
–
PQA2MHAI1$MX
$ThdPPV$phsCA
%
100
THDR Ia
PQA2MHAN1$MX
$ThdAmp
PQA2MHAI1$MX$ThdA$phsA
%
101
THDR Ib
–
–
PQA2MHAI1$M
X$ThdA$phsB
–
PQA2MHAI1$MX
$ThdA$phsB
%
102
THDR Ic
–
–
PQA2MHAI1$M
X$ThdA$phsC
–
PQA2MHAI1$MX
$ThdA$phsC
%
103
Pst (a-n)
PQA2MFLK1$MX
$PhPst
–
–
–
PQA2MFLK1$MX$PhPst
$phsA
–
Data-Points Mapping
1.5 Measured Values
16
SICAM, Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97, Manual
E50417-H1040-C621-A2, Edition 01.2020