Table of Contents

SICAM RTUs, SICAM MIC System Description

9

MC6-054-2.00, Edition 07.2014

A.6.1.2

Packages ............................................................................................. 80

A.6.2

Web  Engineering ....................................................................................... 80

Summary of Contents for SICAM MIC

Page 1: ... 00 SICAM RTUs SICAM MIC System Description Preface Table of Contents Introduction 1 System Overview 2 Function Packages 3 Ambient Conditions 4 System Components and Technical Data 5 Order Information A Glossary ...

Page 2: ...l is checked at regular intervals and any corrections that might become necessary are included in the next releases Any suggestions for improvement are welcome Subject to change without prior notice Document Label SIC1703 SYBSICAMMIC ENG_V2 00 Release Date 2014 07 23 Copyright Copyright Siemens AG 2014 The reproduction transmission or use of this document or its contents is not permitted without e...

Page 3: ...le specifications Evaluation of quotation criteria such as technical specifications of the system or environ mental conditions Conceptual activities such as design and configuration Recommendations for Third Party Products Siemens does neither receive liability nor warranty for recommendations which are given or implied by this manual For the correct and intended use of the respective product the ...

Page 4: ...her Support For more information please contact our Customer Support Center Phone 49 0 180 524 70 00 Fax 49 0 180 524 24 71 charges depending on provider e mail support ic siemens com The Siemens Power Academy offers a comprehensive program of professional training events in the fields of power generation distribution and transmission Main training centers are Nuremberg Germany Head Office Phone 4...

Page 5: ...onary measures are not carried out Warning Means that death serious bodily injury or considerable property damage can occur if the appropriate precautionary measures are not carried out Caution Means that minor bodily injury or property damage can occur if the appropriate precautionary measures are not carried out Note Is important information about the product the handling of the product or the r...

Page 6: ...ltages Severe injury or damage to property can occur if the appropri ate measures are not taken Hazardous voltages can be present on all switching components connected to the power supply Even after the supply voltage has been disconnected hazardous voltages can still be pre sent in the equipment capacitor storage The limit values indicated in the manual or the operating instructions must not be e...

Page 7: ...uration Notes 24 2 3 3 2 TM Peripheral Bus 25 2 4 Communication 26 2 4 1 Process Communication and Engineering 26 2 4 2 Transmission Modes 27 2 4 3 Configurations 28 2 4 3 1 Multi Point Traffic 29 2 4 3 1 1 Dial Up Traffic 30 2 4 3 1 2 LAN WAN 32 2 4 3 1 3 Internet GPRS 33 2 5 Engineering 34 2 5 1 Integrated Webserver for Simple Applications 34 2 5 2 TOOLBOX II 34 3 Function Packages 35 3 1 System...

Page 8: ...0 AI 6307 AI 6308 58 5 4 1 4 AI 6310 59 5 4 1 5 TE 6430 59 5 4 2 Postprocessing and Output 60 5 4 2 1 DO 6200 60 5 4 2 1 1 Further Functions 60 5 4 2 2 DO 6212 61 5 4 2 2 1 Further Functions 61 5 4 2 3 DO 6220 DO 6221 DO 6230 62 5 4 2 3 1 Further Functions 62 5 4 2 4 AO 6380 63 5 4 3 Return Information to Pulse Command Assignment 64 A Order Information 67 A 1 Power Supply Modules 68 A 2 Master Con...

Page 9: ...Table of Contents SICAM RTUs SICAM MIC System Description 9 MC6 054 2 00 Edition 07 2014 A 6 1 2 Packages 80 A 6 2 Web Engineering 80 ...

Page 10: ...Table of Contents 10 SICAM RTUs SICAM MIC System Description MC6 054 2 00 Edition 07 2014 ...

Page 11: ...SICAM RTUs SICAM MIC System Description 11 MC6 054 2 00 Edition 07 2014 1 Introduction Contents 1 1 Compact Telecontrol System SICAM MIC 12 1 2 SICAM MIC The Advantages 14 ...

Page 12: ...igned for DIN rail mounting Practical engineering Great importance was placed on keeping the engineering process as simple as possible That s why the master control element has an integrated Web server for configuration diag nostics and testing so no special tools or additional licenses are needed The tool is already integrated in SICAM MIC and is operated with a standard Web browser Alternatively...

Page 13: ...ogrammable application programs for local control functions complete the all round versatility of the SICAM MIC The SICAM MIC can be used optionally in multipoint or dial up traffic but also over LAN WAN networks Transmission conforms to IEC 60870 5 101 or IEC 60870 5 104 Good connections to the control center Multipoint traffic External data transmission equipment can be connected via the V 28 in...

Page 14: ...OLBOX II Integrated remote maintenance remote diagnostics and remote parameterization Application programs for local controls and interlocks Plug Play for start up and servicing through use of flash card or SIM card for data stor age Exchange of modules without need for a tool Direct connection of the process cables Mounting on 35 mm DIN rail Temperature range 25 C to 70 C 1 2 2 Various Fields of ...

Page 15: ...CAM RTUs SICAM MIC System Description 15 MC6 054 2 00 Edition 07 2014 2 System Overview Contents 2 1 Performance 16 2 2 Mechanical Structure 17 2 3 Architecture 19 2 4 Communication 26 2 5 Engineering 34 ...

Page 16: ...Saving of firmware and application data on replaceable SIM card Communication with other automation units according to IEC 60870 5 101 multipoint traf fic dial up traffic point to point traffic Communication with control center according to IEC 60870 5 104 Ethernet TCP IP or according to IEC 60870 5 101 dial up traffic Standard protocols according to IEC 60870 5 101 104 Spontaneous acknowledged tr...

Page 17: ...The sequence of modules from left to right or top to bottom is prescribed as follows 1 power supply module optionally 2 for redundancy 1 master control module Optionally up to 8 I O modules The electrical connection of the modules with the power supply takes place during the process of latching together whereby each module can be individually replaced Standard Structure 8 I O Modules max Master Co...

Page 18: ...on MC6 054 2 00 Edition 07 2014 Redundant Power Supply not suitable for power enhancement 2 Line Arrangement 8 I O Modules max Master Control Module Power Supply Module Power Supply Module in total max 8 I O modules Master control module Power supply module ...

Page 19: ...equipment for multi point traffic and dial up traffic Features and Functions Installation on DIN rail Input voltages alternatively 24 60 VDC 110 220 VDC System voltage output U1 5 1 VDC max 8 W System voltage output U2 switchable 5 2 VDC max 2 5 W or 10 VDC max 2 5 W Environmental conditions according to EMC Removable screw terminals Supervision of the output voltage Can be connected in parallel f...

Page 20: ... inputs and outputs as well as a lighted display On the master control module CP 6040 resides addition ally an interface for the communication via Ethernet The master control element contains all the central functions for processing and communica tion and it provides the parameter settable telecontrol function and the open closed loop func tion Furthermore the master control element is able to sto...

Page 21: ... RS 232 for multi point or dial up traffic acc to IEC 60870 5 101 with an external data transmission facility Parameter settable telecontrol functions with or without time tagging Central processing functions Application program for open closed loop control functions Decentral archive DEAR Engineering diagnostic and test using webbrowser Storage of parameters and application program on SIM card Lo...

Page 22: ...process data according to IEC 60870 5 101 104 with and without time tag Single point and double point information items Count pulses Actual values Postprocessing and output of process data according to IEC 60870 5 101 104 Single point information items Single point and double point commands Setpoint commands Secured data exchange between the I O modules and the master control element via the TM bu...

Page 23: ...ls and postprocessing by means of hardware binary outputs analog outputs currents and voltages Status display for binary signals Function display via LED Product Overview Type Designation Power DI 6100 Binary input 2x8 24 60 VDC 170 mW DI 6101 Binary input 2x8 110 220 VDC 170 mW DI 6102 Binary input 2x8 24 60 VDC 1 ms 170 mW DI 6103 Binary input 2x8 110 220 VDC 1 ms 170 mW DI 6104 Binary input 2x8...

Page 24: ...the following rules are to be considered Only 1 command output basic module may be connected alternatively DO 6220 command output according to IC1 DO 6221 command output according to RC1 The command output via DO 6220 or DO 6221 without a DO 6230 is not possible Up to 7 command output relay modules DO 6230 may be connected The command output via DO 6230 without a DO 6220 or DO 6221 is not possible...

Page 25: ... control module The communication takes place in the master slave process wherein the I O modules are the slaves The I O modules are automatically addressed on the TM bus based on the sequence of phys ical fitting The I O module connected directly to the peripheral control module has the least significant address The I O modules are checked cyclically for functioning via the TM bus A failure is de...

Page 26: ...ng use the serial interface exclusively and therefore are not available simul taneously CP 6040 CPC60 RS 232 Ethernet LAN Process communication is not available simultaneously using both interfaces with supply for external modem The following transmission facilities can be supplied directly from the power supply module us ing a special cable Type Designation Power typ Supply 1 CE 0700 V 23 leased ...

Page 27: ...onnection RS 232 Digital radio Analog radio CM 0827 optical Dial Up Traffic Unbalanced interchange circuit V 24 V 28 up to 19 2 kbps depends on the used data transmis sion device Time synchronization via serial inter face Efficient message transmission ac cording to IEC 60870 5 101 se quence of information objects SMS messages when using a GSM data transmission device Coherent Technologies Eurocom...

Page 28: ...ocol variant there are different communication methods available Multi point traffic Dial up traffic Single Master Multi Master Communication via LAN WAN Communication via Intranet GPRS TCP IP 60870 5 104 LAN WAN Ethernet TCP IP Radio Fibre Optics Cable etc IEC 60870 5 101 Multi Point Traffic Control System Dial up Traffic PSTN ISDN GSM IEC 60870 5 101 ...

Page 29: ...54 2 00 Edition 07 2014 2 4 3 1 Multi Point Traffic Ethernet TCP IP IEC 60870 5 104 CP 6040 CP 6040 IEC 60870 5 101 unbalanced master of the Ax 1703 family ACP 1703 family or third party manufacturer Radio fiber optic copper cable etc IEC 60870 5 101 Control center ...

Page 30: ...cription MC6 054 2 00 Edition 07 2014 2 4 3 1 1 Dial Up Traffic Single Master Dial Up Traffic PSTN ISDN GSM IEC 60870 5 1 Ethernet TCP IP IEC 60870 5 104 CP 6040 CP 6040 Control center IEC 60870 5 101 unbalanced master of the Ax 1703 or ACP 1703 family ...

Page 31: ... MIC System Description 31 MC6 054 2 00 Edition 07 2014 Multi Master Dial Up Traffic IEC 60870 5 101 PSTN ISDN GSM Ethernet TCP IP IEC 60870 5 104 CP 6040 CP 6040 IEC 60870 5 101 unbalanced master of the Ax 1703 family Control center ...

Page 32: ...System Overview 32 SICAM RTUs SICAM MIC System Description MC6 054 2 00 Edition 07 2014 2 4 3 1 2 LAN WAN Ethernet TCP IP IEC 60870 5 104 CP 6040 CP 6040 Control center ...

Page 33: ... P K R X E R x T X S I 3 S I 2 S I 1 S I 0 LOC F B M PRE 2 M PRE 3 M PRE 0 M PRE 1 NC TB PWR 24 60VDC PUSH TO UNLOC K E R C OM C PY R Y R E S SI0 SI2 F B SI1 E TO SI3 RELEAS E PUSH TO R ELEASE PU SH TO X2 1 2 3 4 5 6 PSTN Internet Router Router Firewall Corporate Network Firewall CP 6040 Base station controller Telecontrol sub station Telecontrol center Data packages P h o n e c a l l s Master sta...

Page 34: ...ction list can be uploaded into the automation unit for execution 2 5 2 TOOLBOX II Of course SICAM MIC supports also the TOOLBOX II the integrated engineering system for the entire SICAM RTUs family This comprises all stages of plant configuration and mainte nance this means data collection configuring parameter setting expanding changing test ing system diagnosis and documentation The introductio...

Page 35: ...SICAM RTUs SICAM MIC System Description 35 MC6 054 2 00 Edition 07 2014 3 Function Packages Contents 3 1 System Services 36 3 2 Telecontrol 37 3 3 Automation 38 ...

Page 36: ...control Addressing Time management Central clock of the automation unit Setting and keeping the own clock s time with a resolution of 10 ms Synchronization via serial communication with another automation unit via LAN NTP server or local minute pulse General interrogation Monitoring functions Failure management Diagnosis and signaling Storing firmware and parameters on a SIM card ...

Page 37: ... up traffic Test if stations are reachable An application program may evaluate telephone charges Parameter setup allows the telephone line to be used efficiently with respect to connection charges e g command output possible only if a connection exists Process Periphery Acquisition and preprocessing of local peripheraly monitor direction Single point and double point information items Counting pul...

Page 38: ...04 Change management and generation of messages with time tag Open closed loop control function via freely definable application programs Creation as function diagram according to IEC 61131 3 with CAEx plus Alternatively creation of an instruction list using an ASCII editor Online diagnostics Transmission of periodic process information between the open closed loop control function and the I O mod...

Page 39: ... MIC System Description 39 MC6 054 2 00 Edition 07 2014 4 Ambient Conditions Contents 4 1 Protection Type 40 4 2 Mechanical Ambient Conditions 41 4 3 Climatic Ambient Conditions 42 4 4 Electromagnetic Compatibility 43 ...

Page 40: ... SICAM MIC System Description MC6 054 2 00 Edition 07 2014 4 1 Protection Type Operational Equipment Protection type acc to IEC 60529 Protection class acc to IEC 61140 CP 60xx IP40 Terminals IP 20 2 I O modules IP40 Terminals IP 20 2 ...

Page 41: ... 200 500 Hz 3 5 mm 10 m s 15 m s IEC 60068 2 6 IEC 60870 2 2 Bm Bm Bm Shock Acceleration 11 ms dura tion function 100 m s IEC 60068 2 27 IEC 60870 2 2 Bm The listed values cover or exceed the required seismic loading according to IEC 60870 2 2 Cl S3 and IEC 60255 21 3 Cl 1 The values apply in operation and for storage The permitted mechanical stresses during transport depend on the transport packa...

Page 42: ... up to 3000 m IEC 60870 2 2 C2 IEC 60654 1 C2 The listed values apply for the use in open air cabinets for bay devices The products can be ex posed to sun and heat They can be exposed as well to air flow caused by draught in buildings e g by open windows or influences of technical processes Bedewing is possible for a short time e g during the course of maintenance tasks not in opera tion Condensat...

Page 43: ...stand Cl Discharge of static elec tricity ESD 8 kV L 6 kV K IEC 61000 4 2 IEC 60870 2 1 3 IEC 60255 22 2 3 Electromagnetic fields 10 V m IEC 61000 4 3 IEC 60870 2 1 3 IEC 60255 22 3 3 50 Hz magnetic fields 30 A m IEC 61000 4 8 IEC 60870 2 1 3 Pulse shaped magnetic fields 300 A m IEC 61000 4 9 IEC 60870 2 1 Radio interference field strength 10 m 40 47 dBµV CISPR22 IEC 60870 2 1 A CISPR22 A ...

Page 44: ...70 2 1 DC3 IEC 60654 2 DC3 Voltage ripple DC 5 IEC 60870 2 1 IEC 60870 2 1 VR3 IEC 60654 2 Starting current S1 IEC 60870 4 IEC 60870 4 S1 Impulse voltage 100 1300µs 1 normal 1 3 UN IEC 61000 4 1 IEC 60870 2 1 Fast transient burst common 4 0 kVs IEC 61000 4 4 2 IEC 60870 2 1 4 IEC 60255 22 4 3 Surge 1 2 50 ms common 4 0 kVs IEC 61000 4 5 IEC 60870 2 1 4 Surge 1 2 50 ms normal 4 0 kVs IEC 61000 4 5 ...

Page 45: ...f TE 6420 If sensor and TE 6420 reside within a cabinet the signal lines to the sensor must be carried out shielded and massed both ways cabinet feeding potential equalization of sensor With usage of third party supplied sensors the signal lines as well as the power supply of the sensor must be directed in shielded cables The power supply may be directed max 1 m un shielded between power supply mo...

Page 46: ...2 00 Edition 07 2014 4 4 5 Communication LAN Parameter Value Test standard Cl Product stand Cl Fast transient burst common 2 0 kV IEC 61000 4 4 IEC 60870 2 1 3 IEC 60255 22 4 4 Induced HF voltage 10 V IEC 61000 4 6 The listed values apply for a distance 100 m cat 5 cable ...

Page 47: ...System Description 47 MC6 054 2 00 Edition 07 2014 5 System Components and Technical Data Contents 5 1 Mechanical Design 48 5 2 Power Supply Modules 49 5 3 Master Control Modules 51 5 4 Peripheral Element and I O Modules 55 ...

Page 48: ...Power supply module approx 200 230 g type specific Master control module approx 280 g I O modules approx 225 300 g type specific Connectors Connection system for peripheral signals and power supply Removeable screw terminals wire cross section up to 2 5 mm Ethernet LAN communication RJ45 socket connector 8 pole for connecting Cat 5 cable RS 232 communication D SUB 9 pole male with additional suppl...

Page 49: ...U1 PU2 hU2 Pin max 12 3 W Pin peak 13 8 W Inrush peak current 8 A at 18 VDC 600 µs 40 A at 78 VDC 600 µs Guaranteed interruption time Reverse voltage protection Yes Overload protection No 3 Short circuit protection No 3 Fault output max switching voltage max output current max short time current 350 VAC VDC 120 mA permanent on resistance 35 Ω 350 mA for 10 ms Mechanics Terminals Removable screw te...

Page 50: ...Inrush peak current 25 A at 90 VDC 500 µs 80 A at 230 VDC 500 µs Guaranteed interruption time Reverse voltage protection Yes Overload protection No 3 Short circuit protection No 3 Fault output max switching voltage max output current max short time current 350 VAC VDC 120 mA permanent on resistance 35 Ω 350 mA for 10 ms Mechanics Terminals Removable screw terminals for direct conductor assembly cr...

Page 51: ...4 Byte Program sampling cyclical 2 2000 ms settable raster 1 ms spontaneous settable run not based on interrupt Acquisition grid digital I O 10 ms or 1 ms depending on I O module Acquisition grid analog I O 500 ms 60 s TE 6430 0 2 ms Decentralized archive Recording raster for measured values 1 2 3 5 10 15 30 60 min settable max message length of a segment 1 200 Byte settable Memory configuration s...

Page 52: ...e load L R 7 ms Switching capacity resistive load min 1 mW max 60 W Nominal switching capacity Nominal switching current 48 W 24 VDC 2 00 A 60 W 48 VDC 1 25 A 60 W 60 VDC 1 00 A Output circuits 18 78 VDC operated by means of external voltage Communication Serial interface Levels according to V 28 ESD protection Transmission rate up to 19 2 kbps depends on the modem Supply for external modem via in...

Page 53: ...sampling cyclically 2 2000 ms settable raster 1 ms spontaneous settable run not based on interrupt Acquisition grid digital I O 10 ms or 1 ms depending on I O module Acquisition grid analog I O 500 ms 60 s TE 6430 0 2 ms Decentralized archive Recording raster for measured values 1 2 3 5 10 15 30 60 min settable max message length of a segment 1 200 Byte settable Memory configuration settable 3 fil...

Page 54: ...d min 1 mW max 60 W Nominal switching capacity Nominal switching current 48 W 24 VDC 2 00 A 60 W 48 VDC 1 25 A 60 W 60 VDC 1 00 A Output circuits 18 78 VDC operated by means of external voltage Communication Serial interface Levels according to V 28 ESD protection Transmission rate up to 19 2 kbps depends on the modem LAN interface Ethernet Ethernet according IEEE 802 3 10Base T Transmission rate ...

Page 55: ... are described in detail in the manual SICAM RTUs Com mon Functions Peripheral Elements according to IEC 60870 5 101 104 Note You find the technical data of the I O modules in the manual SICAM TM I O Modules In the following listing footnotes are used to specify the effect of the functions in detail f Telecontrol the function affects process information which is spontaneously transmitted f1 Teleco...

Page 56: ...control function if larger Revision ta Power monitoring ta Inversion ta Firmware filter t Bounce suppression t Monitoring intermediate and faulty positions t Determination of the cause of transmission t Reporting switching operations in progress t Breaker tripping detection t Breaker tripping suppression during auto reclose t Spontaneous transmission of changes t Periodical transmission a Integrat...

Page 57: ...rger Revision ta Power monitoring ta Inversion ta Firmware filter t Bounce suppression t Monitoring intermediate and faulty positions t Determination of the cause of transmission t Reporting switching operations in progress t Breaker tripping detection t Breaker tripping suppression during auto reclose t Spontaneous transmission of changes t Periodical transmission a Integrated totals via count pu...

Page 58: ...t Measurement range settable with a resolution of12 Bit sign t Shrinking the range results in decreasing resolution Revision t Noise rejection t Automatic calibration t Smoothing t Adaptation t Linear normalized technologically scaled or short floating point Suppression of zero range Plausibility check Change monitoring t Spontaneous transmission of changes t ______ not supported by USIO60 USIO61 ...

Page 59: ...date grid HW rev HW rev A 16 Hz 6 8 s 16 Hz 1 68 s 50 Hz 5 6 s 50 Hz 1 44 s 60 Hz 5 2 s 60 Hz 1 36 s Revision Noise rejection Automatic calibration Calibration for 2 wire technique Smoothing Adaptation Temperature value C F conversion using implemented curves Resistance Ω Change monitoring Spontaneous transmission of changes ______ not supported by USIO60 USIO61 5 4 1 5 TE 6430 Integrated totals v...

Page 60: ...nd output time Settable Dependent on the process Return information monitoring Command prolongation Switching sequences Command output for the auto reclose function If outputs of the module are used for pulse commands no outputs of the same module can be used for binary information output Binary information output Selectable behavior on communication failure ta deactivation or retention Deactivati...

Page 61: ...Switching sequences Command output for the auto reclose function If outputs of the module are used for pulse commands no outputs of the same module can be used for binary information output Binary information output Selectable behavior on communication failure ta deactivation or retention Deactivation on module failure ta Spontaneous transmission t or Periodical transmission a If outputs of the mo...

Page 62: ... 6220 command output according to IC1 Idle check Selective activation check DO 6221 command output according to RC1 Idle check Selective activation check Resistance check Current flow information Earth fault check Interference voltage check Command output time Settable Dependent on the process Return information monitoring Command prolongation Periodical control circuit check Switching sequences M...

Page 63: ...a 15 bits sign at 20 mA 10 V Shrinking the range results in decreasing resolution Application functions and procedures according to IEC 60870 5 101 104 ta Formal check Direct command Select and execute command select execute Adaptation t Linear normalized technologically scaled or short floating point t Selectable behavior on communication failure and module failure ta keep value output substitute...

Page 64: ...x IN D17 command IOM y CB07 Single information to single command 1 5 pole DI 610x with DO 6212 two DO 6212 with one DI 610x possible SI IOM x IN D00 command IOM y OUT D00 SI IOM x IN D01 command IOM y OUT D01 SI IOM x IN D06 command IOM y OUT D06 SI IOM x IN D10 command IOM z OUT D00 SI IOM x IN D11 command IOM z OUT D01 SI IOM x IN D16 command IOM z OUT D06 Single information to single command 1 ...

Page 65: ...13 command IOM y CB02 CB03 DI IOM x IN D14 D15 command IOM y CB04 CB05 DI IOM x IN D16 D17 command IOM y CB06 CB07 Double information to double command 1 5 pole DI 610x with DO 6212 two DO 6212 with one DI 610x possible DI IOM x IN D00 D01 command IOM y OUT D00 D01 DI IOM x IN D02 D03 command IOM y OUT D02 D03 DI IOM x IN D04 D05 command IOM y OUT D04 D05 DI IOM x IN D10 D11 command IOM z OUT D00 ...

Page 66: ...System Components and Technical Data 66 SICAM RTUs SICAM MIC System Description MC6 054 2 00 Edition 07 2014 ...

Page 67: ...ystem Description 67 MC6 054 2 00 Edition 07 2014 A Order Information Contents A 1 Power Supply Modules 68 A 2 Master Control Modules 69 A 3 I O Modules 70 A 4 Interface Modules 73 A 5 Accessories 74 A 6 Engineering Tools 79 ...

Page 68: ...IC System Description MC6 054 2 00 Edition 07 2014 A 1 Power Supply Modules Designation Item Number MLFB PS 6630 Power supply module 24 60 VDC EMC GC6 630 6MF11130GG300AA0 PS 6632 Power supply module 110 220 VDC EMC GC6 632 6MF11130GG320AA0 ...

Page 69: ... Description 69 MC6 054 2 00 Edition 07 2014 A 2 Master Control Modules Designation Item Number MLFB CP 6020 Master control module V 28 8 modules GC6 020 6MF11130GA200AA0 CP 6040 Master control module ET10TX V 28 8 modules GC6 040 6MF11130GA400AA0 ...

Page 70: ... Number MLFB DI 6100 Binary input 2x8 24 60 VDC GC6 100 6MF11130GB000AA0 DI 6101 Binary input 2x8 110 220 VDC GC6 101 6MF11130GB010AA0 DI 6102 Binary input 2x8 24 60 VDC 1 ms GC6 102 6MF11130GB020AA0 DI 6103 Binary input 2x8 110 220 VDC 1 ms GC6 103 6MF11130GB030AA0 DI 6104 Binary input 2x8 220 VDC GC6 104 6MF11130GB040AA0 ...

Page 71: ...0 VDC GC6 200 6MF11130GC000AA0 DO 6212 Binary output relays 8x 24 220 VDC 230 VAC GC6 212 6MF11130GC120AA0 DO 6220 Command output Basic module GC6 220 6MF11130GC200AA0 DO 6221 Command output Basic module measurement GC6 221 6MF11130GC210AA0 DO 6230 Command output Relay module GC6 230 6MF11130GC300AA0 AI 6300 Analog input 2x2 20 mA 10 V GC6 300 6MF11130GD000AA0 ...

Page 72: ... Analog input 2x2 2 5 mA 5 mA 10 V GC6 307 6MF11130GD070AA0 AI 6308 Analog input 2x2 1 mA 2 mA 10 V GC6 308 6MF11130GD080AA0 AI 6310 Analog input 2x2 Pt100 Ni100 GC6 310 6MF11130GD100AA0 AO 6380 Analog output 4x 20 mA 10 mA 10 V GC6 380 6MF11130GD800AA0 TE 6420 Speed measurement 2x2 5 VDC 24 VDC NAMUR GC6 420 6MF11130GE200AA0 ...

Page 73: ...lvanically insulated GA0 819 6MF11112AJ100AF0 CM 0821 Fieldbus interface ring 3x FO 1x el GA0 821 6MF11110AJ210AA0 CM 0822 Fieldbus interface star 4x FO GA0 822 6MF11110AJ220AA0 CM 0823 Fieldbus interface ring 3x FO 1x RS485 GA0 823 6MF11110AJ230AA0 CM 0827 Fibre optic interface El FO GA0 827 6MF11110AJ270AA0 CM 0829 RS 232 RS 422 RS 485 Converter GA0 829 6MF11112AJ200AA0 ...

Page 74: ...ng G22 081 6MF11020CA810AA0 withdrawn A 5 2 Recommended Modems Third Party Devices Designation Item Number MLFB Westermo TD 36AV 22 264 VAC 18 300 VDC Westermo TD 36LV 10 30 VAC 10 60 VDC Dial up traffic analog www westermo com Westermo IDW 90 Dial up traffic ISDN www westermo com Coherent Eurocom 24 Dial up traffic analog G21 014 6MF11020BA140AA0 Cinterion MC52iT Dual band Dial up traffic GSM inc...

Page 75: ...C52iT modem 220 mm 9 pole D SUB TC6 211 6MF13130GC110AA1 DSUB 9 pole connector locking TC6 212 6MF13130GC120AA1 TPP_1M TP Patch cable 1m Cat5 grey TPP_2M TP Patch cable 2m Cat5 grey TPP_3M TP Patch cable 3m Cat5 grey TPP_5M TP Patch cable 5m Cat5 grey TPP_10M TP Patch cable 10m Cat5 grey for cabinet internal wirings T41 255 6MF13040BC550AA0 T41 251 6MF13040BC510AA0 T41 252 6MF13040BC520AA0 T41 253...

Page 76: ...re optics length max 1 5 km FO INDOORCABLE 62 DUP LSOH FO OUTDOORCABLE 62 2FIB ARM TF7 006 6MF13140HA060AA1 TF7 007 6MF13140HA070AA1 FO CONNECTOR ST 50 62 TF7 016 6MF13140HA160AA1 Modular coupler RJ45 9 pole D SUB female TF5 101 6MF13140FB010AA1 CM 6810 TM I O modules extension cable GC6 810 6MF11130GJ100AA0 A 1 1 Recommanded Upstream Power Supply Units Designation Item number MLFB Power supply 11...

Page 77: ...Coding section for TM terminal strip TC6 055 6MF13130GA550AA0 Tool for disconnecting the plug in TC6 200 6MF13130GC000AA0 PHOENIX CR MSTB Coding section is inserted on the multi pin connector directly on the terminal module red insulating mate rial 6 pcs PHO 1734401 WEIDMUELLER LPA QB2 Cross connection 2 pins WEI 147220 WEIDMUELLER Sheet with 48 sticky labels For individual labelling of the termin...

Page 78: ...tion 07 2014 Designation Item Number MLFB PHOENIX Zack band ZB 8 27 For labeling with BMKL 26 8 x 6 8 WH laser printer labels M PEN or CMS system lettering field 8 x 27 mm white 10 pcs PHO 0807216 WAGO End bracket 249 117 Snap on end bracket for TS35 rail WAG 249 117 www wago de ...

Page 79: ...00 5 6MF14030FA000AA5 TBII_OPMII Light_V5_Licence S35 010 5 6MF14030FA100AA5 TBII_OPMII Light to FULL_V5_Licence S35 011 5 6MF14030FA110AA5 Tool for open closed loop control functions TBII_CAExplus_V5_Licence S36 100 5 6MF14030GB000AA5 TBII_CAExplus Light_V5_Licence S36 110 5 TBII_CAExplus Light to FULL_V5_Licence S36 111 5 Expansion for Safety V V Safety Monitor TBII_CAEx_safety_V5_Licence S36 20...

Page 80: ...ftware licenses are required An extensiv selection of software licenses depending on need and configuration is available Local PC configuration Server client configuration Web engineering Update Upgrade LIGHT to FULL The order of the software licenses takes place via the MLFB that starts for V5 0 always with 6MF7050 and for V5 1 always with 6MF7051 Through the selection of the options results the ...

Page 81: ...processing for the control of a machine or of a process with a PLC system acc to IEC 61131 12 1 With CAEx plus application programs for open closed loop control functions are created An application program comprises the task s and the related program instances and type instances An application pro gram is executed by a resource CPU Application service data unit The application service data unit AS...

Page 82: ...interpreted as target address Ax 1703 peripheral bus Enables the secured hamming distance 4 serial system internal communication between the basic sys tem element and the peripheral elements Ax PE Bus Ax 1703 peripheral bus B Basic system element System element for processing of information according to different criterions e g automation telecontrol etc and for the administration of system functi...

Page 83: ... only upon interrogation by the central station Command direction Transmission facility from the central station to a substation Command return information The command return information is an additional information for the double point information displays the reason for the status change breaker tripping or switching operation in progress Configuration Configuration is used in a multiple meaning...

Page 84: ...ntrol line of a RS 232 interface for the evaluation of the receive signal level DCE Data Communications Equipment for example a modem DDC Data Distribution Center Tool for the export import and or administration of SICAM TOOLBOX II data Detailed diagnostic record Comprises 16 diagnostic bits of a system diagnostic class that commonly belong logically together Detailed diagnostic table Contains all...

Page 85: ...ile Allocation Table FAT16 up to 2 GB FAT32 as of 32 GB capacity Fieldbus interface processor The fieldbus interface processor serves for the serial connection of SICAM RTUs systems to a Profibus Profibus Master Profibus Slaves are connected acc to EN 50170 2 FIP Fieldbus interface processor Firewall Blockage of a local network or computer against not allowed access from a supraregional network Fu...

Page 86: ...ISDN Integrated Standard for Digital Network K L LAN Local Area Network Load share operation Redundant communication via 2 interfaces whereby the messages are partitioned in undisturbed opera tion on both interfaces according to particular rules dependent on load or priority Local parameter Parameter that is managed on the own module firmware and is used only there M MDI Media Dependent Interface ...

Page 87: ... If the output pulse is set and a command output binary output is already selected relay activated the command is output to the process P PBA Peripheral Module Address PCM Puls Code Modulation PE Peripheral Element Peridocal control circuit check The periodical control circuit check detects if the command circuits are ready to function correctly without activating the actuator Control circuits are...

Page 88: ... they can be easily integrated into an industrial control system and easily used in all their intended functions IEC 61131 1 chapter 2 50 Protocol element The protocol element is a supplementary system element for communication with other automation units or control systems It comunicates via the internal bus ZBG Bus with the basic system element PSR SICAM TOOLBOX II configuration tool PSTN Public...

Page 89: ...ingle point information Monitored information represented by only one bit characterizing two determined states of operational equipment SMS Short Message Service transmission of up to 160 characters SNMP Simple Network Management Protocol SNMP is a network protocol to monitor and control network components e g router switches server printer from a central station SNTP Simple Network Time Protocol ...

Page 90: ... and that is not available to the user It can be transported through the system like a periodical information or like a spontaneous information object A system internal information is only mentioned in order to explain the behavior of the described func tions T TAP Telocator Alphanumeric Protocol TCP IP Transmission Control Protocol Internet Protocol TETRA Terrestrial trunked radio universal platf...

Page 91: ...ition 07 2014 V VAC Volts of Alternating Current VDC Volts of Direct Current VPN Virtual Private Network logical connection for secure transmission of data via internet W WAN Wide Area Network Web services Web standard for function calls between independent devices X Z ...

Page 92: ...Glossary 92 SICAM RTUs SICAM MIC System Description MC6 054 2 00 Edition 07 2014 ...

Reviews: