Figure 10.
Anchoring Outdoor OGM Non-Walk-In Switchgear
UPPER BREAKER THROUGH TOP
UPPER BREAKER THROUGH BOTTOM
0
2
1
0
0
0
0
0
(AREA C)
MAXIMUM AVAILABLE SPACE FOR
CUSTOMER PRIMARY CONNECTION
FROM LOWER BREAKER THRU BOTTOM OR
FROM LOWER BREAKER THRU TOP OR
CUSTOMER PRIMARY CONNECTION
MAXIMUM AVAILABLE SPACE FOR
SECONDARY LEADS BELOW OR ABOVE
PREFERRED LOCATION FOR CUSTOMER
LEFT HAND SIDE (OPTIONAL)
WITHDRAWAL
FOR BREAKER
(RECOMMENDED)
ALLOW 76"
FLOOR PLAN
REAR
OF FRAME
SIDE)
FRONT
FLOOR
LINE
DRAWOUT
(BREAKER
OF FRAME
FR
ONT
CUSTOMER CONDUIT IS NOT
TO EXTEND MORE THAN
7.0" ABOVE FLOOR LINE.
LOCATION OF .75" DIA. ANCHOR BOLTS.
BOLTS & NUTS FURNISHED BY CUSTOMER.
CLAMP WASHERS FURNISHED BY SIEMENS.
ANCHOR BOLTING ARRANGEMENT
TYPE 'OGM' SWITCHGEAR
(AREA A)
(AREA B)
SEE FIGURE 7 FOR EXPLANATION
OF CABLE AREAS
36.0
36.0
94.0
7.38
2.38
31.0
.12
.12
2.38
3.75
7.0
ALLOW 30.0"
CLEARANCE FOR
DOOR SWING ON
LEFT HAND END.
FLOOR MUST BE LEVEL 48.0"
IN FRONT OF SWITCHGEAR TO
ALLOW PROPER OPERATION OF
CIRCUIT BREAKER LIFT TRUCK.
ALLOW 6.0"
FOR BREAKER
WITHDRAWAL
.50
6.0
.75
91.25
1.0
4.63
1.12 PANEL
92.75
.75
14.25
11.0
26.0
5.0
15.76
4.25
8.75
10.12
Installation
13