Document No. 129-479 
Installation Instructions 
November 13, 2012 

 

CAUTION: 

 

Follow manufacturer’s Installation 
Instructions and Wiring Guidelines for 
connecting the controller to the Room Unit. 

 

TALON Controllers with common 
already earth grounded are TXIO used 
on TC Modular and TC Compact 36 
Expansion. These do not require the 
earth ground wire to be connected to 
the controller as shown in Figure 9. 

 

TALON Controllers with floating 
common are TC Compact 16/24/36, 
Raptor, Predator and PPM. These 
require the earth ground wire to be 
connected to the controller as shown in 
Figure 9. 

NOTE: 

If active temperature (0-5V/0-10V/4-20 mA) (Pin 
3) rather than passive/ resistive temperature is 
used, Passive Temp Common (Pin 6) does not 
need to be terminated. 

NOTE: 

To use the override function with a Predator 
Controller, a 500 ohm resistor must be wired in 
series with the setpoint termination on the 
Predator Controller and the Override termination 
8 on the Room Sensor. See Figure 6 and Figure 
7 for the complete wiring diagrams for the two 
different style controllers. 

The installation is now complete. 

1
2
3
4
5
6

7
8
9

10
11
12

SEN0485R1

 

Figure 5.  Typical Wiring Base. 

(All terminals may not be present.) 

 

 
 
 
 
 
 
 
 
 

Pin No. 

Function 

QAA2312.EWTN 

2 Temperature 
3 Temp_Common 

QAA2330.EWxC

 

2 Temperature 
3 Temp_Common 
7 LON1 
8 LON2 

QAA23SS.EWxN

 

 

DC+ or ACH 

 

DC- or ACN (GND) 

 3 

Temperature 

Output 

 5* 

Passive 

Temp 

 

6* 

Passive Temp Common 

QAA23xx.FWxN 

 

DC + or ACH 

 

DC - or ACN (GND) 

 3 

Temperature 

Output 

 5* 

Passive 

Temp 

 

6* 

Passive Temp Common 

 7 

Setpoint 

Output 

 8 

Override 

 9 

Override 

Common 

QAA2330.FWTC

 

 

DC + or ACH 

 

DC - or ACN (GND) 

 3 

Temperature 

Output 

 5* 

Passive 

Temp 

 

6* 

Passive Temp Common 

 7 

Setpoint 

Output 

 8 

Override 

 9 

Override 

Common 

 10 

GND 

 11 

LON1 

 12 

LON2 

* Not available on “SS” models. 

Page 4

 

of

 

6

 

Siemens Industry, Inc.

 

Summary of Contents for Series 2300

Page 1: ...QAA2330 xWxx QAA23SS xWxN QAA23SS xWxx Accessories AQA2200 INTL Room Unit Back Plate 10 pack AQA2200 2X4 Room Unit Back Plate Single NOTE If installing the Back Plate discard the metric screws provided with the Back Plate and utilize the Room Unit mounting screws Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Expected Installation...

Page 2: ...o plastic wall anchors flush to below the wall surface for stable mounting of the device 3 Cut a 1 inch 25 mm center hole with a hole saw 4 Pull about three inches 75 mm of the cable through the hole in the base plate 5 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior t...

Page 3: ... locator by removing the two screws and lightly rocking the locator to pull it free 2 Untie the twist tie and pull about three inches 75 mm of the room unit cable through the hole in the base plate 3 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior to mounting to the wa...

Page 4: ...or Controller a 500 ohm resistor must be wired in series with the setpoint termination on the Predator Controller and the Override termination 8 on the Room Sensor See Figure 6 and Figure 7 for the complete wiring diagrams for the two different style controllers The installation is now complete 1 2 3 4 5 6 7 8 9 10 11 12 SEN0485R1 Figure 5 Typical Wiring Base All terminals may not be present Pin N...

Page 5: ...0644R1 500 ohm Orange White Orange White Green White Blue Blue Green 5 SetPoint Bypass 6 Room Temp 2 LonNetwork 4 Common 3 Service Pin LCD Power 1 LonNetwork Color Pin Wire Twisted Pair Twisted Pair Twisted Pair P I 9 11 Figure 7 Pin No Function QAA2312 EWTN 2 Temperature 3 Temp_Common QAA2330 EWxC 2 Temperature 3 Temp_Common 7 LON1 8 LON2 QAA23SS EWxN 1 DC or ACH 2 DC or ACN GND 3 Temperature Out...

Page 6: ...300 100 VA DC ACH DC ACN GND Signal Out Powered By Class 2 100VA Isolated AC L N E With Class 2 100 VA Output Isolated AC Supply See Controller Installation Instructions L N E Note See Caution NOTE Externally AC powered 2300 Room Units require controller common and all AC secondary neutral ACN to be earth grounded and may be used on the same controller with other room units powered by internal sen...

Reviews: