Commissioning
6.3 Parameterizing the device
PAC2200
72
Equipment Manual, 12/2019, L1V30415167B-03
"Integrated I/O" parameter
"Digital input" parameter
The following functions can be assigned to the "Digital input" parameter:
●
Tariff switching for two-tariff, active energy, and reactive energy counters.
●
Synchronization of the demand period by means of the synchronization pulse of a system
control center
or other device.
Selection
Range
Factory setting
ACTION
NONE:
Input is deactivated.
PULSE INPUT:
Counting of input pulses
HT/LT SWITCHING:
Switching between tariffs. Low tariff if input active.
DEMAND SYNC:
Synchronization of power demand.
NONE
UNIT
The "UNIT" property is only visible if "PULSE INPUT" is set for
the "ACTION".
Countable unit with pulse counting:
Active Energy (kWh)
Reactive Energy (kvarh)
—
PULSES PER
UNIT
The "PULSES PER UNIT" property is only visible if "PULSE
INPUT" is set for the "ACTION".
Range: 1 to 4000
1
PRO
(input pulse di-
vider)*
The "PULSES PER UNIT" property is only visible if "PULSE
INPUT" is set for the "ACTION".
Range: 1; 10; 100; 1000
1
)* Formula:
Example:
Pulses per unit: 50
Pulse divider: 100
Unit: kWh
Summary of Contents for SENTRON PAC2200
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200 6 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200 12 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 40: ...Description 2 5 Communication PAC2200 38 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 54: ......
Page 84: ...Service and maintenance 7 5 Warranty PAC2200 82 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 96: ...Technical specifications 8 2 Labeling PAC2200 94 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 129: ......
Page 130: ......