Accessories
4.3 Connection system
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
269
4.3.3.2
Auxiliary conductor terminal
A control wire tap can be implemented easily using components from the 3VA molded case
circuit breaker equipment portfolio.
1)
Maximum current carrying capacity 15 A
Note
A maximum current limit of 15 A applies to all control wire taps for 3VA molded case circuit
breakers and must not be exceeded.
The control wire tap must be taken into account when configuring the molded case circuit
breaker. Suitable cable cross-sections: Cables up to a maximum of 2.5 mm
2
can be
connected.