![Siemens SCALANCE X-200 Operating Instructions Manual Download Page 168](http://html.mh-extra.com/html/siemens/scalance-x-200/scalance-x-200_operating-instructions-manual_379379168.webp)
Configuration / diagnostics using remote mechanisms
6.3 Configuration using Web Based Management (WBM) and Command Line Interface (CLI)
SCALANCE X-200
168
Operating Instructions, 12/2011, A5E00349864-19
●
Copy internal Configuration to C-PLUG and Restart
The configuration in the internal flash memory of the switch is copied to the C-PLUG and
this is followed by a restart.
Use case:
The IE Switch X-200 starts up with a C-PLUG inserted. This contains a configuration that
differs from the IE Switch X-200 or a configuration containing errors. With this function,
you can overwrite the content of the C-PLUG with the original device configuration.
●
Copy default Configuration to C-PLUG and Restart
This stores the configuration with all factory default values on the C-PLUG. This is
followed by a restart during which the IE Switch X-200 restarts with these default values.
●
Clean C-PLUG (Low Level Format, Configuration lost)
Deletes all data from the C-PLUG and triggers low-level formatting. This is not followed
by an automatic restart and the device displays an error. You can clear this error status
by restarting or removing the C-PLUG after turning off the basic device. To retain the
configuration of the basic device even after deleting the C-PLUG, the configuration data
stored on the C-PLUG is transferred to the internal memory of the basic device.
●
Continue without C-PLUG
If the C-PLUG is removed from a device, an error message is displayed after the device
restarts. In this case, you can select the "Continue without C-PLUG" option to change the
device to the mode without a C-PLUG.
Your selection is then adopted when you click "Modify".
Syntax of the Command Line Interface
Table 6- 3
C-PLUG Information - CLI\SYSTEM\C-PLUG>
Command
Description
Comment
info
Displays the current status (information) of the C-PLUG.
initdef
Initializes the C-PLUG with the default parameters and
restarts the device.
Administrator only.
initmem
Initializes the C-PLUG with the MEMORY parameters and
restarts the device.
Administrator only.
usecplug [D]
If the C-PLUG was removed, the next time you restart the
device, an error command is displayed in the Command
Line Interface.
By entering the useplug D command, you can change the
device to operate in the mode without C-PLUG.
Administrator only.
clear
Erases the data on the C-PLUG.
Administrator only.
Summary of Contents for SCALANCE X-200
Page 12: ...Table of contents SCALANCE X 200 12 Operating Instructions 12 2011 A5E00349864 19 ...
Page 284: ...Technical specifications SCALANCE X 200 284 Operating Instructions 12 2011 A5E00349864 19 ...
Page 288: ...References SCALANCE X 200 288 Operating Instructions 12 2011 A5E00349864 19 ...
Page 294: ...Dimension drawings SCALANCE X 200 294 Operating Instructions 12 2011 A5E00349864 19 ...