Technical Specifications
5
This section provides important technical specifications related to the device.
5.1
Power Supply Specifications
Note
When determining cable lengths, make sure the minimum input voltage for the pow-
er supply is provided at the power source.
Input Range
Power Sup-
ply Type
Min
Max
Internal
Fuse Rating
Maximum
Power Con-
sumption
a
Insulation
88 VDC
300 VDC
HI
85 VAC
264 VAC
3.15 A(T)
b
65 W
88 VDC
300 VDC
HIP
85 VAC
264 VAC
3.15 A(T)
b
65 W
2800 VDC
for 1 minute
24
24P
13 VDC
36 VDC
10 A(T)
b
63.5 W
48
48P
36 VDC
72 VDC
3.15 A(T)
b
60 W
1500 VDC
for 1 minute
12
12P
9 VDC
15 VDC
12 A
67 W
1500 VAC or
2121 VDC
for 1 minute
a
Power consumption varies based on the device configuration.
b
(T) denotes time-delay fuse.
5.2
Failsafe Relay Specifications
Maximum Switching Voltage
Rated Switching Current
Isolation
30 VDC
5 A
125 VDC
0.1 A
a
, 0.15 A
b
250 VAC
6.25 A
2800 VDC for 1 minute be-
tween coil and contacts
a
Inductive load R/L = 7 ms
b
Resistive load
RUGGEDCOM RX1501
Installation Manual, 05/2020, C79000-G8976-1054-17
45