Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Signal Ports
2.5 kV Common
Mode @ 1 MHz
IEEE 1613
Oscillatory
DC Power Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
Signal Ports
5 kV (Failsafe Relay)
DC Power Ports
5 kV
IEEE 1613
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV (Failsafe Relay)
DC Power Ports
2.8 kVDC or 2 kV
IEEE 1613
Dielectric
Strength
AC Power Ports
2 kV
IEEE 1613.1
IEC 61000-4-10
Damped
Oscillat-
ing Mag-
netic Field
Enclosure Ports
100 A/m for 1 s (100
kHz and 1 MHz)
Environmental Type Tests
Test
Description
Test Levels
Severity Levels
Cold Temperature
Test Ad
-40 °C (-40
°F), 16 Hours
IEC 60068-2-1
Cold Storage
Test Ab
-40 °C (-40
°F), 16 Hours
Dry Heat
Test Bd
85 °C (185
°F), 16 Hours
IEC 60068-2-2
Dry Heat Storage
Test Bd
85 °C (185
°F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Dd
95% (Non-Con-
densing), 55 °C
(131 °F), 6 Cycles
IEC 60068-2-14
Change of
Temperature
Test Nb
5 Cycles @
-40 to 85 °C
(-40 to 185 °F)
IEC 60068-2-78
Humidity (Damp
Heat, Cyclic)
Test Cab
10 Days @ 55 °C
(131 °F), 6 Cycles
IEC 60255-21-1
Vibration
2 g @ 10 to 150 Hz
Class 2
IEC 60255-21-2
Shock
30 g @ 11 ms
Class 2
IEC 60255-21-2
Bump
10 g @ 16 ms
Class 1
IEC 60255-21-3
Seismic
Method A
Class 2
IEC 60529
Ingress Protection
IP4x
42
RUGGEDCOM RSG909R
Installation Manual, 02/2020, C79000-G8976-1388-09