Chapter 6
Certification
RUGGEDCOM RS950G
Installation Guide
30
Other Approvals
Section 6.1.8
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
•
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Requirements
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS950G has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity Levels
Enclosure Contact
± 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
RUGGEDCOM-
specified
severity levels.
Signal Ports
± 4 kV @ 2.5 kHz
Note
a
DC Line-to-Line
± 4 kV
4
AC Line-to-Line
± 4 kV
4
IEC 61000-4-4
Burst (Fast Transient)
Earth Ground Ports
± 4 kV
4
Signal Ports
± 4 kV Line-to-Ground, ± 2 kV Line-to-Line
4
DC Line-to-Line
± 2 kV Line-to-Ground, ± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Line-to-Line
± 4 kV Line-to-Ground, ± 2 kV Line-to-Line
4
Signal Ports
10 V
3
DC Line-to-Line
10 V
3
AC Line-to-Line
10 V
3
IEC 61000-4-6
Induced
(Conducted) RFI
Earth Ground Ports
10 V
3
40 A/m continuous, 1000 A/m for 1 s
RUGGEDCOM-
specified
severity levels.
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
DC Line-to-Line
30% for 0.1 s, 60% for 0.1 s, 100% for 0.05 s
IEC 61000-4-29
Voltage Dips
and Interrupts
AC Line-to-Line
30% for 1 period, 60% for 50 periods
Summary of Contents for RUGGEDCOM RS950G
Page 4: ...RUGGEDCOM RS950G Installation Guide iv ...
Page 10: ...Preface RUGGEDCOM RS950G Installation Guide x Customer Support ...
Page 30: ...Chapter 4 Communication Ports RUGGEDCOM RS950G Installation Guide 20 SFP Transceivers ...
Page 36: ...Chapter 5 Technical Specifications RUGGEDCOM RS950G Installation Guide 26 Dimension Drawings ...