Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severi-
ty Levels
DC Pow-
er Ports
30 V Continuous
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply
DC Pow-
er Ports
10%
3
IEC
61000-4-29
Voltage Dips and Interrupts
DC Pow-
er Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports 2 kV (Failsafe Relay Output)
DC Pow-
er Ports
1.5 kV
Dielectric Strength
AC Pow-
er Ports
2 kV
Signal Ports 5 kV (Failsafe Relay Output)
DC Pow-
er Ports
5 kV
IEC 60255-5
HV Impulse
AC Pow-
er Ports
5 kV
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RS910 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports. Class 1 allows for temporary communica-
tion loss, while Class 2 requires error-free and interrupted communications.
Description
Test Levels
Enclosure Contact
± 8 kV
ESD
Enclosure Air
± 15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
± 4 kV @ 2.5 kHz
DC Power Ports
± 4 kV
AC Power Ports
± 4 kV
Fast Transient
Earth Ground Ports
± 4 kV
Signal Ports
2.5 kV Common Mode @ 1 MHz
DC Power Ports
2.5 kV Common and Dif-
ferential Mode @ 1 MHz
Oscillatory
AC Power Ports
2.5 kV Common and Dif-
ferential Mode @ 1 MHz
Signal Ports
5 kV (Failsafe Relay)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV (Failsafe Relay)
Dielectric Strength
DC Power Ports
1.5 kV
40
RUGGEDCOM RS910
Installation Manual, 02/2020, C79000-G8976-1029-09