RUGGEDCOM RMC
Installation Guide
Chapter 6
Certification
Other Approvals
25
• CAN ICES-3 (A)/NMB-3 (A)
Section 6.1.6
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
•
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3: General Requirements
•
NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RMC has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity Levels
Enclosure Contact
± 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Note
a
Signal Ports
± 4 kV @ 2.5 kHz
Note
a
DC Power Ports
± 4 kV
4
AC Power Ports
± 4 kV
4
IEC 61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV
4
Signal Ports
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
4
DC Power Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
4
Signal Ports
10 V
3
DC Power Ports
10 V
3
AC Power Ports
10 V
3
IEC 61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V
3
Summary of Contents for RUGGEDCOM RMC
Page 10: ...Chapter 1 Introduction RUGGEDCOM RMC Installation Guide 4 Description ...
Page 22: ...Chapter 3 Communication Ports RUGGEDCOM RMC Installation Guide 16 Fiber Optic Ethernet Ports ...
Page 34: ...Chapter 6 Certification RUGGEDCOM RMC Installation Guide 28 EMC and Environmental Type Tests ...