Siemens RDY2000 Installation Instructions Manual Download Page 8

Document No. 129-905 
Installation Instructions 
March 26, 2015 
 

Page 8 of 18 

 

Siemens Industry, Inc. 

 

 

Table 3.  100 Series Parameters*. 

Parameter 

Definition 

Display 

Value Range 

Default 

Extended Definition 

Notes 

P101 

System Type 

SYS TYPE 

CO 

HP 

CO 

CO = Conventional System 
HP = Heat Pump 

  

P102 

Cooling 
Stages 

COOL STGS 




Sets number of cooling stages. 

  

P103 

Heating 
Stages 

HEAT STGS 




Sets number of heating stages. 

  

P104 

Aux Heating 
Stages 

AUX HT STG 



Sets number of auxiliary heat stages 
available for heat pump control. 

This parameter only 
appears if P101 = HP. 

P105 

Fan Operation 

HTG FAN 

NO 

(YES if 

P101=HP) 

YES 

YES = Fan Relay energized by thermostat 

on call for heat 

NO =  Fan relay not energized by 

thermostat on call for heat 

If HVAC unit does not 
start fan on call for 
heat, set P105 to YES. 

P106 

Reversing 
Valve 

REV VALVE 

O =  Energize reversing valve on cooling 
B =  Energize reversing valve on heating 

This parameter only 
appears if P101 = HP. 

P107 

Scheduler 
Days 

SCHEDULER 





0 =  Disable Scheduler 
1 =  Schedule all days with 

same 

schedule 

2 =  One schedule for M-F and another for 

Sat + Sun 

3 =  One schedule for M-F, Sat + Sun 

scheduled individually 

7 =  Schedule each day individually 

See Table 9 through 
Table 13. 

P108 

Program 
Periods 

PERIODS 


Sets number of program periods per day: 

2 = 2 periods (Day/Night) 
4 = 4 periods (Wake/Day/Evng/Night) 

This parameter only 
appears if P107 > 0. 

P109 

Units 

UNITS 

NOTE: Changing temperature units will reset all temperature-

related parameters to their default values.

 

P110 

Auto Change 

AUTO CHNGE 

YES 

NO 

YES 

 Enables auto change between heating and 
cooling. 

This parameter does 
not appear on systems 
that are heat only or 
cool only. 

P111 

Changeover 
Deadband 

DEADBAND 

3°F  to 9°F 

(2.0°C to 

5.0°C) 

5°F 

(3.0°C) 

Changeover deadband in degrees F (C) 

This parameter does 
not appear if P110 = 
NO. 
 
This parameter forces a 
separation between 
heating and cooling 
setpoints to prevent 
short cycling of 
heating/cooling cycles. 

P112 

Daylight 
Savings 

DAYLT SAVE 

NO 

YES 

YES 

Y =  Auto adjust for Daylight Savings Time 
N =  Does not auto adjust for Daylight 

Savings Time 

Daylight Savings Time 
adjustment is based on 
USA schedule. 

* Included in Set-up Wizard

 

Summary of Contents for RDY2000

Page 1: ...ss of data may occur if you do not follow the procedures as specified Required Tools No 1 Phillips screwdriver 1 8 flat blade screwdriver Drill with 1 8 drill bit Expected Installation Time 15 minutes CAUTION The RDY2000 is an advanced controller designed to be installed by professional HVAC technicians Installation by non qualified personnel may result in degraded system efficiency occupant disco...

Page 2: ...ving Jumper RC C3 See Wiring Diagrams Figure 6 5 Attach thermostat to the base plate by engaging tabs at the top and rotating the thermostat downward until it is securely seated on the base plate 6 Secure the thermostat to the base plate with the Phillips screws provided using the holes at the bottom of the housing The installation is now complete Restore power and continue to Thermostat Setup The...

Page 3: ...ion relay is on Cool Mode The system is actively in cooling mode Heat Mode The system is actively in heating mode Heating Cooling Stages Each segment represents one stage of heating or cooling Auxiliary Heating Auxiliary heating stage AUX Stage 1 Aux 2 Stage 2 Service Reminders and Fault Messages Service reminders appear at the right side of the screen SERVICE UV LAMP SERVICE HUMIDIFIER SERVICE AI...

Page 4: ...Document No 129 905 Installation Instructions March 26 2015 Page 4 of 18 Siemens Industry Inc Wiring Diagrams Figure 4 Wiring Schematic Conventional System ...

Page 5: ...Document No 129 905 Installation Instructions March 26 2015 Siemens Industry Inc Page 5 of 18 Figure 5 Wiring Schematic Heat Pump Figure 6 Wiring Schematic Aux Output 3 ...

Page 6: ...can be modified For instance if the thermostat is in heating mode only the heating setpoint displays and can be modified If the thermostat is in AUTO mode both the heating and cooling setpoints will be displayed and can be modified 3 Use the left and right arrows to access the different setpoints and the and icons to adjust the setpoints 4 Touch the center of the screen to exit Setpoint Programmin...

Page 7: ...the screen is locked To unlock the keypad do the following 1 Touch the center of the Home screen to access the room temperature screen 2 Press the Settings icon once and LOCKED displays 3 Press and hold the Settings icon for 5 seconds PASSWORD displays 4 Using the lower left and right arrows enter the INSTALLER password 5 Press PASSWORD to accept the password 6 Set Parameter 211 Keypad Lockout to ...

Page 8: ... 1 2 3 7 2 0 Disable Scheduler 1 Schedule all days with same schedule 2 One schedule for M F and another for Sat Sun 3 One schedule for M F Sat Sun scheduled individually 7 Schedule each day individually See Table 9 through Table 13 P108 Program Periods PERIODS 2 4 2 Sets number of program periods per day 2 2 periods Day Night 4 4 periods Wake Day Evng Night This parameter only appears if P107 0 P...

Page 9: ...5 F 7 0 C OFF Heat pump compressor will not operate below this outdoor temp forcing unit to auxiliary heat An outdoor temperature sensor is required NOTE If P206 OFF set P508 1 F 0 5 C This parameter only appears for the following conditions P101 HP P104 0 P105 YES P301 P305 P309 or P313 5 P206 P207 P207 Heat Pump Auxiliary Heat Lockout HP AUX LO OFF 40 F 4 0 C 45 F 7 0 C 50 F 10 0 C 55 F 13 0 C 6...

Page 10: ...9 0 0 Not Used 1 Indoor Temperature Remote 2 Indoor Temperature Average 3 Supply Temp 4 Return Temp 5 Outdoor Temp 6 Humidity 0 10V 7 CO2 0 10V 8 Occupancy DI 9 Fault Selections for Inputs 1 4 cannot be duplicated If set to 9 fault a DI causes SERVICE REQUIRED segment to activate See Table 14 for a list of optional sensors approved for use with the RDY2000 P306 Temperature Input 2 Type TMP IN 2 0 ...

Page 11: ... 0V 40 F 4 4 C Only appears if P314 1 P315 P316 P316 Temperature Input 4 High TMP 4 HI P315 value to 250 F 120 0 C 120 F 50 0 C Calibrates thermostat to high end of temp sensor signal at 10 volts for example 10V 250 F 121 1 C Only appears if P314 1 P316 P315 P317 Aux Output 1 OUT1 AUX OUT 1 0 1 2 3 4 5 0 0 Not Used 1 Humidification 2 Dehumidification 3 Occupied 4 Air Quality 5 Economizer Enable Se...

Page 12: ...If Installer Password is changed a new password should be recorded for future reference P701 Firmware Revision FIRMWARE X X N A Read Only Expert Level Menus 1 Touch the center of the Home screen 2 Press the Settings icon SCHEDULER displays 3 Press the left arrow 4 Press INSTALLER 5 Using the lower left and right arrows enter the password 6 Press PASSWORD to accept the password and return the unit ...

Page 13: ...in minutes before system will automatically switch from heating to cooling or vice versa P506 Cooling Deadband CL DEADBND 1 F 0 5 C to 5 F 4 0 C 1 F The deadband is divided equally above and below setpoint Cooling will begin when temperature exceeds upper point of deadband and ceases when temperature falls below lower point of deadband P507 Stage Delay Heating STG DLY HT 1 to 10 minutes 2 Time del...

Page 14: ...gized ON Relay energized P907 Test Output 1 OUT1 TST ON OFF OFF OFF Relay not energized ON Relay energized P908 Test Output 2 OUT2 TST ON OFF OFF OFF Relay not energized ON Relay energized P909 Test Output 3 OUT3 TST ON OFF OFF OFF Relay not energized ON Relay energized P911 Expert Password XPRT PW 50 00 to 99 99 99 99 Auxiliary Sequences The RDY2000 primary sequences are designed to control singl...

Page 15: ...ires a schedule to be configured Occupancy Notification Parameters P301 P305 P309 P313 If the optional occupancy sensor is used one of these must be set to 8 P317 P318 P319 To signal an external device that the space is occupied one of these must be set to 3 P404 If the optional occupancy sensor is used P404 can be used to set a minimum run timer for any actions that are activated by occupancy suc...

Page 16: ...y Evng Night Setpoint Heat F 70 62 70 62 70 68 70 62 70 68 70 62 Setpoint Cool F 75 82 75 82 75 78 75 82 75 78 75 82 Time 6 00 AM 10 00 PM 8 00 AM 10 00 PM 6 00 AM 11 00 AM 1 00 PM 10 00 PM 8 00 AM 11 00 AM 1 00 PM 10 00 PM Table 11 Work Week Schedule with Separate Weekend Days 2 Periods per Day Day Work Week Monday Friday Saturday Sunday Phase Day Night Day Night Day Night Setpoint Heat F 70 62 7...

Page 17: ...lass B digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee tha...

Page 18: ...erature Input 2 Type 0 P307 Temperature Input 2 Low 0 F 18 0 C P308 Temperature Input 2 High 120 F 50 0 C P309 Configurable Input 3 IN3 0 P310 Temperature Input 3 Type 0 P311 Temperature Input 3 Low 0 F 18 0 C P312 Temperature Input 3 High 120 F 50 0 C P313 Configurable Input 4 IN4 0 P314 Temperature Input 4 Type 0 P315 Temperature Input 4 Low 0 F 18 0 C P316 Temperature Input 4 High 120 F 50 0 C ...

Reviews: