background image

Document No. 129-905 

Installation Instructions 

March 26, 2015 

Siemens Industry, Inc.

 

Page 3 of 18

 

Status Bar 

The status bar at the top of the display consists of 
11 icons. 

Table 2.  Status Bar Icons.

 

Icon 

Name 

Meaning 

 

Occupied 

Space is occupied, 
based on Schedule 
and/or Occupancy 
Sensor. 

 

Keypad Lock 

Keypad is locked. 

 

Scheduler 

Unit is running on the 
local schedule. 

 

Override 

The Scheduler is being 
overridden by local 
control. 

 

Humidity 

Control 

Indicator 

Droplet and (+) indicates 
humidification relay is on. 
Droplet and (-) indicates 
dehumidification relay is 
on. If neither relay is on, 
the water droplet does 
not appear. 

 

Fan 

Fan relay is on. 

 

Fresh Air 

Economizer Enable/ 
Ventilation relay is on. 

 

Cool Mode 

The system is actively in 
cooling mode. 

 

Heat Mode 

The system is actively in 
heating mode. 

 

Heating/Cooling 

Stages 

Each segment 
represents one stage of 
heating or cooling. 

 

Auxiliary 

Heating 

Auxiliary heating stage: 
AUX=Stage 1: Aux 
2=Stage 2 

Service Reminders and Fault Messages 
 

 

Service reminders appear at the right side of the 
screen: 

– 

SERVICE UV LAMP 

– 

SERVICE HUMIDIFIER 

– 

SERVICE AIR FILTER 

They are determined by the timer set in the Installer 
Setup Menu, and can be cleared by pressing the 

Settings icon

 [

], and then 

SERVICE

. See 

Clearing Service Reminders

 

Active fault messages appear at the left side of 
the home screen: 

– 

CONNECTION LOST (Not applicable to this 
model) 

– 

DEMAND RESPONSE (Not applicable to 
this model) 

– 

SERVICE REQUIRED (See

 Viewing Fault 

Messages

Fault messages are automatically cleared when the 
root cause of the failure is resolved. 

Summary of Contents for RDY2000

Page 1: ...ss of data may occur if you do not follow the procedures as specified Required Tools No 1 Phillips screwdriver 1 8 flat blade screwdriver Drill with 1 8 drill bit Expected Installation Time 15 minutes CAUTION The RDY2000 is an advanced controller designed to be installed by professional HVAC technicians Installation by non qualified personnel may result in degraded system efficiency occupant disco...

Page 2: ...ving Jumper RC C3 See Wiring Diagrams Figure 6 5 Attach thermostat to the base plate by engaging tabs at the top and rotating the thermostat downward until it is securely seated on the base plate 6 Secure the thermostat to the base plate with the Phillips screws provided using the holes at the bottom of the housing The installation is now complete Restore power and continue to Thermostat Setup The...

Page 3: ...ion relay is on Cool Mode The system is actively in cooling mode Heat Mode The system is actively in heating mode Heating Cooling Stages Each segment represents one stage of heating or cooling Auxiliary Heating Auxiliary heating stage AUX Stage 1 Aux 2 Stage 2 Service Reminders and Fault Messages Service reminders appear at the right side of the screen SERVICE UV LAMP SERVICE HUMIDIFIER SERVICE AI...

Page 4: ...Document No 129 905 Installation Instructions March 26 2015 Page 4 of 18 Siemens Industry Inc Wiring Diagrams Figure 4 Wiring Schematic Conventional System ...

Page 5: ...Document No 129 905 Installation Instructions March 26 2015 Siemens Industry Inc Page 5 of 18 Figure 5 Wiring Schematic Heat Pump Figure 6 Wiring Schematic Aux Output 3 ...

Page 6: ...can be modified For instance if the thermostat is in heating mode only the heating setpoint displays and can be modified If the thermostat is in AUTO mode both the heating and cooling setpoints will be displayed and can be modified 3 Use the left and right arrows to access the different setpoints and the and icons to adjust the setpoints 4 Touch the center of the screen to exit Setpoint Programmin...

Page 7: ...the screen is locked To unlock the keypad do the following 1 Touch the center of the Home screen to access the room temperature screen 2 Press the Settings icon once and LOCKED displays 3 Press and hold the Settings icon for 5 seconds PASSWORD displays 4 Using the lower left and right arrows enter the INSTALLER password 5 Press PASSWORD to accept the password 6 Set Parameter 211 Keypad Lockout to ...

Page 8: ... 1 2 3 7 2 0 Disable Scheduler 1 Schedule all days with same schedule 2 One schedule for M F and another for Sat Sun 3 One schedule for M F Sat Sun scheduled individually 7 Schedule each day individually See Table 9 through Table 13 P108 Program Periods PERIODS 2 4 2 Sets number of program periods per day 2 2 periods Day Night 4 4 periods Wake Day Evng Night This parameter only appears if P107 0 P...

Page 9: ...5 F 7 0 C OFF Heat pump compressor will not operate below this outdoor temp forcing unit to auxiliary heat An outdoor temperature sensor is required NOTE If P206 OFF set P508 1 F 0 5 C This parameter only appears for the following conditions P101 HP P104 0 P105 YES P301 P305 P309 or P313 5 P206 P207 P207 Heat Pump Auxiliary Heat Lockout HP AUX LO OFF 40 F 4 0 C 45 F 7 0 C 50 F 10 0 C 55 F 13 0 C 6...

Page 10: ...9 0 0 Not Used 1 Indoor Temperature Remote 2 Indoor Temperature Average 3 Supply Temp 4 Return Temp 5 Outdoor Temp 6 Humidity 0 10V 7 CO2 0 10V 8 Occupancy DI 9 Fault Selections for Inputs 1 4 cannot be duplicated If set to 9 fault a DI causes SERVICE REQUIRED segment to activate See Table 14 for a list of optional sensors approved for use with the RDY2000 P306 Temperature Input 2 Type TMP IN 2 0 ...

Page 11: ... 0V 40 F 4 4 C Only appears if P314 1 P315 P316 P316 Temperature Input 4 High TMP 4 HI P315 value to 250 F 120 0 C 120 F 50 0 C Calibrates thermostat to high end of temp sensor signal at 10 volts for example 10V 250 F 121 1 C Only appears if P314 1 P316 P315 P317 Aux Output 1 OUT1 AUX OUT 1 0 1 2 3 4 5 0 0 Not Used 1 Humidification 2 Dehumidification 3 Occupied 4 Air Quality 5 Economizer Enable Se...

Page 12: ...If Installer Password is changed a new password should be recorded for future reference P701 Firmware Revision FIRMWARE X X N A Read Only Expert Level Menus 1 Touch the center of the Home screen 2 Press the Settings icon SCHEDULER displays 3 Press the left arrow 4 Press INSTALLER 5 Using the lower left and right arrows enter the password 6 Press PASSWORD to accept the password and return the unit ...

Page 13: ...in minutes before system will automatically switch from heating to cooling or vice versa P506 Cooling Deadband CL DEADBND 1 F 0 5 C to 5 F 4 0 C 1 F The deadband is divided equally above and below setpoint Cooling will begin when temperature exceeds upper point of deadband and ceases when temperature falls below lower point of deadband P507 Stage Delay Heating STG DLY HT 1 to 10 minutes 2 Time del...

Page 14: ...gized ON Relay energized P907 Test Output 1 OUT1 TST ON OFF OFF OFF Relay not energized ON Relay energized P908 Test Output 2 OUT2 TST ON OFF OFF OFF Relay not energized ON Relay energized P909 Test Output 3 OUT3 TST ON OFF OFF OFF Relay not energized ON Relay energized P911 Expert Password XPRT PW 50 00 to 99 99 99 99 Auxiliary Sequences The RDY2000 primary sequences are designed to control singl...

Page 15: ...ires a schedule to be configured Occupancy Notification Parameters P301 P305 P309 P313 If the optional occupancy sensor is used one of these must be set to 8 P317 P318 P319 To signal an external device that the space is occupied one of these must be set to 3 P404 If the optional occupancy sensor is used P404 can be used to set a minimum run timer for any actions that are activated by occupancy suc...

Page 16: ...y Evng Night Setpoint Heat F 70 62 70 62 70 68 70 62 70 68 70 62 Setpoint Cool F 75 82 75 82 75 78 75 82 75 78 75 82 Time 6 00 AM 10 00 PM 8 00 AM 10 00 PM 6 00 AM 11 00 AM 1 00 PM 10 00 PM 8 00 AM 11 00 AM 1 00 PM 10 00 PM Table 11 Work Week Schedule with Separate Weekend Days 2 Periods per Day Day Work Week Monday Friday Saturday Sunday Phase Day Night Day Night Day Night Setpoint Heat F 70 62 7...

Page 17: ...lass B digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee tha...

Page 18: ...erature Input 2 Type 0 P307 Temperature Input 2 Low 0 F 18 0 C P308 Temperature Input 2 High 120 F 50 0 C P309 Configurable Input 3 IN3 0 P310 Temperature Input 3 Type 0 P311 Temperature Input 3 Low 0 F 18 0 C P312 Temperature Input 3 High 120 F 50 0 C P313 Configurable Input 4 IN4 0 P314 Temperature Input 4 Type 0 P315 Temperature Input 4 Low 0 F 18 0 C P316 Temperature Input 4 High 120 F 50 0 C ...

Reviews: