Page 18 of 18
Siemens Industry, Inc.
Table 15. Record Field Settings.
Parameter
Definition
Default
Field Value
P101
System Type
CO
P102
Cooling Stages
2
P103
Heating Stages
2
P104
Aux Heating Stages
0
P105
Fan Operation
NO
P106
Reversing Valve
O
P107
Scheduler Days
2
P108
Program Periods
2
P110
Auto Change
YES
P111
Changeover Deadband
5°F (2.5°C)
P112
Daylight Savings
YES
P201
Heat Temp Limit
95°F (35.0°C)
P202
Cool Temp Limit
50°F (10.0°C)
P203
Temperature Display Offset
0°F (0°C)
P204
Override Time Limit
---
P205
Override Temp Limit
---
P206
Heat Pump Compressor Lock Out
OFF
P207
Heat Pump Auxiliary Heat Lockout
OFF
P208
Service UV Lamp
0
P209
Service Humidifier
0
P210
Service Air Filter
0
P211
Keypad Lockout
0
P213
Backlight
15
P301
Configurable Input 1 (IN1)
0
P302
Temperature Input 1 Type
0
P303
Temperature Input 1 Low
0°F (-18.0°C)
P304
Temperature Input 1 High
120°F (50°C)
P305
Configurable Input 2 (IN2)
0
P306
Temperature Input 2 Type
0
P307
Temperature Input 2 Low
0°F (-18.0°C)
P308
Temperature Input 2 High
120°F (50.0°C)
P309
Configurable Input 3 (IN3)
0
P310
Temperature Input 3 Type
0
P311
Temperature Input 3 Low
0°F (-18.0°C)
P312
Temperature Input 3 High
120°F (50.0°C)
P313
Configurable Input 4 (IN4)
0
P314
Temperature Input 4 Type
0
P315
Temperature Input 4 Low
0°F (-18.0°C)
P316
Temperature Input 4 High
120°F (50.0°C)
P317
Aux Output 1 (OUT1)
0
P318
Aux Output 2 (OUT2)
0
P319
Aux Output 3 (OUT3 & C3)
0
P320
Independent Humidity Control
No
P401
Unit Number
---
P402
CO2 Setpoint
800
P403
Pre-Occupancy Purge
0
P404
Occupancy Sensor Min Run Timer
30
P405
Semi-Continuous Fan
NO
P407
Installer Password
0000
P701
Firmware Revision
N/A
P501
Stage Delay - Cooling
2
P502
Stage Differential - Cooling
1°F (0.5°C)
P503
Cooling Minimum Off Time
5
P504
Cooling Minimum On Time
3
P505
Changeover Delay
10
P506
Cooling Deadband
1°F
P507
Stage Delay - Heating
2
P508
Stage Differential - Heating
Conv. = 1°F (0.5°C); HP = 2°F (1°C)
P509
Heating Minimum Off Time
5
P510
Heating Minimum On Time
5 (10 if heat pump)
P511
Heating Deadband
1°F (0.5°C)
P911
Expert Password
99:99