Siemens RDY2000 Installation Instructions Manual Download Page 18

 

Page 18 of 18

 

Siemens Industry, Inc. 

 

Table 15.  Record Field Settings. 

Parameter 

Definition 

Default 

Field Value 

P101 

System Type 

CO 

 

P102 

Cooling Stages 

 

P103 

Heating Stages 

 

P104 

Aux Heating Stages 

 

P105 

Fan Operation 

NO 

 

P106 

Reversing Valve 

 

P107 

Scheduler Days 

 

P108 

Program Periods 

 

P110 

Auto Change 

YES 

 

P111 

Changeover Deadband 

5°F (2.5°C) 

 

P112 

Daylight Savings 

YES 

 

P201 

Heat Temp Limit 

95°F (35.0°C) 

 

P202 

Cool Temp Limit 

50°F (10.0°C) 

 

P203 

Temperature Display Offset 

0°F (0°C) 

 

P204 

Override Time Limit 

--- 

 

P205 

Override Temp Limit 

--- 

 

P206 

Heat Pump Compressor Lock Out 

OFF 

 

P207 

Heat Pump Auxiliary Heat Lockout 

OFF 

 

P208 

Service UV Lamp 

 

P209 

Service Humidifier 

 

P210 

Service Air Filter 

 

P211 

Keypad Lockout 

 

P213 

Backlight 

15 

 

P301 

Configurable Input 1 (IN1) 

 

P302 

Temperature Input 1 Type 

 

P303 

Temperature Input 1 Low 

0°F (-18.0°C) 

 

P304 

Temperature Input 1 High 

120°F (50°C) 

 

P305 

Configurable Input 2 (IN2) 

 

P306 

Temperature Input 2 Type 

 

P307 

Temperature Input 2 Low 

0°F (-18.0°C) 

 

P308 

Temperature Input 2 High 

120°F (50.0°C) 

 

P309 

Configurable Input 3 (IN3) 

 

P310 

Temperature Input 3 Type 

 

P311 

Temperature Input 3 Low 

0°F (-18.0°C) 

 

P312 

Temperature Input 3 High 

120°F (50.0°C) 

 

P313 

Configurable Input 4 (IN4) 

 

P314 

Temperature Input 4 Type 

 

P315 

Temperature Input 4 Low 

0°F (-18.0°C) 

 

P316 

Temperature Input 4 High 

120°F (50.0°C) 

 

P317 

Aux Output 1 (OUT1) 

 

P318 

Aux Output 2 (OUT2) 

 

P319 

Aux Output 3 (OUT3 & C3) 

 

P320 

Independent Humidity Control 

No 

 

P401 

Unit Number 

--- 

 

P402 

CO2 Setpoint 

800 

 

P403 

Pre-Occupancy Purge 

 

P404 

Occupancy Sensor Min Run Timer 

30 

 

P405 

Semi-Continuous Fan 

NO 

 

P407 

Installer Password 

0000 

 

P701 

Firmware Revision 

N/A 

 

P501 

Stage Delay - Cooling 

 

P502 

Stage Differential - Cooling 

1°F (0.5°C) 

 

P503 

Cooling Minimum Off Time 

 

P504 

Cooling Minimum On Time 

 

P505 

Changeover Delay 

10 

 

P506 

Cooling Deadband 

1°F 

 

P507 

Stage Delay - Heating 

 

P508 

Stage Differential - Heating 

Conv. = 1°F (0.5°C); HP = 2°F (1°C) 

 

P509 

Heating Minimum Off Time 

 

P510 

Heating Minimum On Time 

5 (10 if heat pump) 

 

P511 

Heating Deadband 

1°F (0.5°C) 

 

P911 

Expert Password 

99:99 

 

 

Summary of Contents for RDY2000

Page 1: ...ss of data may occur if you do not follow the procedures as specified Required Tools No 1 Phillips screwdriver 1 8 flat blade screwdriver Drill with 1 8 drill bit Expected Installation Time 15 minutes CAUTION The RDY2000 is an advanced controller designed to be installed by professional HVAC technicians Installation by non qualified personnel may result in degraded system efficiency occupant disco...

Page 2: ...ving Jumper RC C3 See Wiring Diagrams Figure 6 5 Attach thermostat to the base plate by engaging tabs at the top and rotating the thermostat downward until it is securely seated on the base plate 6 Secure the thermostat to the base plate with the Phillips screws provided using the holes at the bottom of the housing The installation is now complete Restore power and continue to Thermostat Setup The...

Page 3: ...ion relay is on Cool Mode The system is actively in cooling mode Heat Mode The system is actively in heating mode Heating Cooling Stages Each segment represents one stage of heating or cooling Auxiliary Heating Auxiliary heating stage AUX Stage 1 Aux 2 Stage 2 Service Reminders and Fault Messages Service reminders appear at the right side of the screen SERVICE UV LAMP SERVICE HUMIDIFIER SERVICE AI...

Page 4: ...Document No 129 905 Installation Instructions March 26 2015 Page 4 of 18 Siemens Industry Inc Wiring Diagrams Figure 4 Wiring Schematic Conventional System ...

Page 5: ...Document No 129 905 Installation Instructions March 26 2015 Siemens Industry Inc Page 5 of 18 Figure 5 Wiring Schematic Heat Pump Figure 6 Wiring Schematic Aux Output 3 ...

Page 6: ...can be modified For instance if the thermostat is in heating mode only the heating setpoint displays and can be modified If the thermostat is in AUTO mode both the heating and cooling setpoints will be displayed and can be modified 3 Use the left and right arrows to access the different setpoints and the and icons to adjust the setpoints 4 Touch the center of the screen to exit Setpoint Programmin...

Page 7: ...the screen is locked To unlock the keypad do the following 1 Touch the center of the Home screen to access the room temperature screen 2 Press the Settings icon once and LOCKED displays 3 Press and hold the Settings icon for 5 seconds PASSWORD displays 4 Using the lower left and right arrows enter the INSTALLER password 5 Press PASSWORD to accept the password 6 Set Parameter 211 Keypad Lockout to ...

Page 8: ... 1 2 3 7 2 0 Disable Scheduler 1 Schedule all days with same schedule 2 One schedule for M F and another for Sat Sun 3 One schedule for M F Sat Sun scheduled individually 7 Schedule each day individually See Table 9 through Table 13 P108 Program Periods PERIODS 2 4 2 Sets number of program periods per day 2 2 periods Day Night 4 4 periods Wake Day Evng Night This parameter only appears if P107 0 P...

Page 9: ...5 F 7 0 C OFF Heat pump compressor will not operate below this outdoor temp forcing unit to auxiliary heat An outdoor temperature sensor is required NOTE If P206 OFF set P508 1 F 0 5 C This parameter only appears for the following conditions P101 HP P104 0 P105 YES P301 P305 P309 or P313 5 P206 P207 P207 Heat Pump Auxiliary Heat Lockout HP AUX LO OFF 40 F 4 0 C 45 F 7 0 C 50 F 10 0 C 55 F 13 0 C 6...

Page 10: ...9 0 0 Not Used 1 Indoor Temperature Remote 2 Indoor Temperature Average 3 Supply Temp 4 Return Temp 5 Outdoor Temp 6 Humidity 0 10V 7 CO2 0 10V 8 Occupancy DI 9 Fault Selections for Inputs 1 4 cannot be duplicated If set to 9 fault a DI causes SERVICE REQUIRED segment to activate See Table 14 for a list of optional sensors approved for use with the RDY2000 P306 Temperature Input 2 Type TMP IN 2 0 ...

Page 11: ... 0V 40 F 4 4 C Only appears if P314 1 P315 P316 P316 Temperature Input 4 High TMP 4 HI P315 value to 250 F 120 0 C 120 F 50 0 C Calibrates thermostat to high end of temp sensor signal at 10 volts for example 10V 250 F 121 1 C Only appears if P314 1 P316 P315 P317 Aux Output 1 OUT1 AUX OUT 1 0 1 2 3 4 5 0 0 Not Used 1 Humidification 2 Dehumidification 3 Occupied 4 Air Quality 5 Economizer Enable Se...

Page 12: ...If Installer Password is changed a new password should be recorded for future reference P701 Firmware Revision FIRMWARE X X N A Read Only Expert Level Menus 1 Touch the center of the Home screen 2 Press the Settings icon SCHEDULER displays 3 Press the left arrow 4 Press INSTALLER 5 Using the lower left and right arrows enter the password 6 Press PASSWORD to accept the password and return the unit ...

Page 13: ...in minutes before system will automatically switch from heating to cooling or vice versa P506 Cooling Deadband CL DEADBND 1 F 0 5 C to 5 F 4 0 C 1 F The deadband is divided equally above and below setpoint Cooling will begin when temperature exceeds upper point of deadband and ceases when temperature falls below lower point of deadband P507 Stage Delay Heating STG DLY HT 1 to 10 minutes 2 Time del...

Page 14: ...gized ON Relay energized P907 Test Output 1 OUT1 TST ON OFF OFF OFF Relay not energized ON Relay energized P908 Test Output 2 OUT2 TST ON OFF OFF OFF Relay not energized ON Relay energized P909 Test Output 3 OUT3 TST ON OFF OFF OFF Relay not energized ON Relay energized P911 Expert Password XPRT PW 50 00 to 99 99 99 99 Auxiliary Sequences The RDY2000 primary sequences are designed to control singl...

Page 15: ...ires a schedule to be configured Occupancy Notification Parameters P301 P305 P309 P313 If the optional occupancy sensor is used one of these must be set to 8 P317 P318 P319 To signal an external device that the space is occupied one of these must be set to 3 P404 If the optional occupancy sensor is used P404 can be used to set a minimum run timer for any actions that are activated by occupancy suc...

Page 16: ...y Evng Night Setpoint Heat F 70 62 70 62 70 68 70 62 70 68 70 62 Setpoint Cool F 75 82 75 82 75 78 75 82 75 78 75 82 Time 6 00 AM 10 00 PM 8 00 AM 10 00 PM 6 00 AM 11 00 AM 1 00 PM 10 00 PM 8 00 AM 11 00 AM 1 00 PM 10 00 PM Table 11 Work Week Schedule with Separate Weekend Days 2 Periods per Day Day Work Week Monday Friday Saturday Sunday Phase Day Night Day Night Day Night Setpoint Heat F 70 62 7...

Page 17: ...lass B digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee tha...

Page 18: ...erature Input 2 Type 0 P307 Temperature Input 2 Low 0 F 18 0 C P308 Temperature Input 2 High 120 F 50 0 C P309 Configurable Input 3 IN3 0 P310 Temperature Input 3 Type 0 P311 Temperature Input 3 Low 0 F 18 0 C P312 Temperature Input 3 High 120 F 50 0 C P313 Configurable Input 4 IN4 0 P314 Temperature Input 4 Type 0 P315 Temperature Input 4 Low 0 F 18 0 C P316 Temperature Input 4 High 120 F 50 0 C ...