Siemens RDY2000 Installation Instructions Manual Download Page 12

Document No. 129-905 
Installation Instructions 
March 26, 2015 
 

Page 12 of 18

 

Siemens Industry, Inc. 

 

Table 6.  400 Series Parameters. 

Parameter 

Definition 

Display 

Value 

Range 

Default 

Extended Definition 

Notes 

P401 

Unit Number 

UNIT NMBR 

1 to 999 

--- 

Allows HVAC unit number to be 
displayed on thermostat home screen. 

 

P402 

CO2 Setpoint 

CO2 SET PT 

500 to 

2000 
PPM 

800 

If CO2 level, as measured by an 
external sensor exceeds setpoint, the 
Ventilation sequence is initiated. 

For optimum human 
performance, CO2 levels 
should be kept below 1000 
parts per million. 

P403 

Pre-

Occupancy 

Purge 

PRE OC PRG 




hours 

0 = Disabled 
1 = 1 Hour 
2 = 2 Hours 
3 = 3 Hours 

Pre-Occupancy Purge will 
energize the Economizer 
Enable and Fan relays prior 
to the start of the first 
scheduled occupancy period. 
Not applicable to systems 
without a schedule. 

P404 

Occupancy 
Sensor Min 

Run Timer 

OCC MRT 

3 to 60 

minutes 

30 

Minimum run time to remain in 
Occupied mode upon receipt of signal 
from Occupancy Sensor. 

Only shown if an input is set 
to Occupancy Sensor. 

P405 

Semi-

Continuous 

Fan 

CONT FAN 

No 

Yes 

NO 

Fan relay will be continuously energized 
when space is occupied, as determined 
by schedule or external Occupancy 
Sensor.  

Only shown if a schedule is 
present or if an input is 
configured for Occupancy 
Sensor. 

P407 

Installer 

Password 

INSTALL PW 

00:00 to 

49.99 

00:00 

NOTE: 

 If Installer Password is changed, a new password should be 
recorded for future reference.  

P701 

Firmware 

Revision 

FIRMWARE 

X.X 

N/A 

Read Only 

 

Expert Level Menus 

1.  Touch the center of the Home screen. 

2.  Press the 

Settings icon

 [

]. 

SCHEDULER

 

displays. 

3.  Press the left [

] arrow. 

4.  Press 

INSTALLER

5.  Using the lower left [

] and right [

] arrows, 

enter the password. 

6.  Press 

PASSWORD

 to accept the password and 

return the unit to the Setup Menu. 

NOTE: 

 The Expert Level default password is 

99:99

.

 

7.  See Table 3 through Table 8 and 

Wiring 

Diagrams

 for additional information. 

8.  Press the 

Settings icon

 [

] to accept changes 

and return the unit to the Home screen. 

 

Recovering a Lost Password

 

If either of the default passwords is changed, the new 
password(s) should be recorded and maintained for 
future reference. If the records are misplaced, the 
following procedure can be used to set new passwords: 

1.  Cycle power to the thermostat. This can be done 

by loosening the securing screws on the bottom 
of the housing and momentarily separating the 
thermostat from the base plate. 

2.  Within 50 seconds of restoring power, navigate 

to the Installer Set-up screen and enter 

98:21

 as 

the passcode. 

3.  The thermostat will go directly to the Expert 

Level password screen. A new Expert Level 
password can now be set. 

4.  After setting a new Expert Level password, the 

thermostat will return to the Home screen. 

5.  The new Expert Level password can be used to 

enter the full Expert Level set-up menu where 
both the Expert Level and Installer Level 
passwords can now be set to new values. 

 

Summary of Contents for RDY2000

Page 1: ...ss of data may occur if you do not follow the procedures as specified Required Tools No 1 Phillips screwdriver 1 8 flat blade screwdriver Drill with 1 8 drill bit Expected Installation Time 15 minutes CAUTION The RDY2000 is an advanced controller designed to be installed by professional HVAC technicians Installation by non qualified personnel may result in degraded system efficiency occupant disco...

Page 2: ...ving Jumper RC C3 See Wiring Diagrams Figure 6 5 Attach thermostat to the base plate by engaging tabs at the top and rotating the thermostat downward until it is securely seated on the base plate 6 Secure the thermostat to the base plate with the Phillips screws provided using the holes at the bottom of the housing The installation is now complete Restore power and continue to Thermostat Setup The...

Page 3: ...ion relay is on Cool Mode The system is actively in cooling mode Heat Mode The system is actively in heating mode Heating Cooling Stages Each segment represents one stage of heating or cooling Auxiliary Heating Auxiliary heating stage AUX Stage 1 Aux 2 Stage 2 Service Reminders and Fault Messages Service reminders appear at the right side of the screen SERVICE UV LAMP SERVICE HUMIDIFIER SERVICE AI...

Page 4: ...Document No 129 905 Installation Instructions March 26 2015 Page 4 of 18 Siemens Industry Inc Wiring Diagrams Figure 4 Wiring Schematic Conventional System ...

Page 5: ...Document No 129 905 Installation Instructions March 26 2015 Siemens Industry Inc Page 5 of 18 Figure 5 Wiring Schematic Heat Pump Figure 6 Wiring Schematic Aux Output 3 ...

Page 6: ...can be modified For instance if the thermostat is in heating mode only the heating setpoint displays and can be modified If the thermostat is in AUTO mode both the heating and cooling setpoints will be displayed and can be modified 3 Use the left and right arrows to access the different setpoints and the and icons to adjust the setpoints 4 Touch the center of the screen to exit Setpoint Programmin...

Page 7: ...the screen is locked To unlock the keypad do the following 1 Touch the center of the Home screen to access the room temperature screen 2 Press the Settings icon once and LOCKED displays 3 Press and hold the Settings icon for 5 seconds PASSWORD displays 4 Using the lower left and right arrows enter the INSTALLER password 5 Press PASSWORD to accept the password 6 Set Parameter 211 Keypad Lockout to ...

Page 8: ... 1 2 3 7 2 0 Disable Scheduler 1 Schedule all days with same schedule 2 One schedule for M F and another for Sat Sun 3 One schedule for M F Sat Sun scheduled individually 7 Schedule each day individually See Table 9 through Table 13 P108 Program Periods PERIODS 2 4 2 Sets number of program periods per day 2 2 periods Day Night 4 4 periods Wake Day Evng Night This parameter only appears if P107 0 P...

Page 9: ...5 F 7 0 C OFF Heat pump compressor will not operate below this outdoor temp forcing unit to auxiliary heat An outdoor temperature sensor is required NOTE If P206 OFF set P508 1 F 0 5 C This parameter only appears for the following conditions P101 HP P104 0 P105 YES P301 P305 P309 or P313 5 P206 P207 P207 Heat Pump Auxiliary Heat Lockout HP AUX LO OFF 40 F 4 0 C 45 F 7 0 C 50 F 10 0 C 55 F 13 0 C 6...

Page 10: ...9 0 0 Not Used 1 Indoor Temperature Remote 2 Indoor Temperature Average 3 Supply Temp 4 Return Temp 5 Outdoor Temp 6 Humidity 0 10V 7 CO2 0 10V 8 Occupancy DI 9 Fault Selections for Inputs 1 4 cannot be duplicated If set to 9 fault a DI causes SERVICE REQUIRED segment to activate See Table 14 for a list of optional sensors approved for use with the RDY2000 P306 Temperature Input 2 Type TMP IN 2 0 ...

Page 11: ... 0V 40 F 4 4 C Only appears if P314 1 P315 P316 P316 Temperature Input 4 High TMP 4 HI P315 value to 250 F 120 0 C 120 F 50 0 C Calibrates thermostat to high end of temp sensor signal at 10 volts for example 10V 250 F 121 1 C Only appears if P314 1 P316 P315 P317 Aux Output 1 OUT1 AUX OUT 1 0 1 2 3 4 5 0 0 Not Used 1 Humidification 2 Dehumidification 3 Occupied 4 Air Quality 5 Economizer Enable Se...

Page 12: ...If Installer Password is changed a new password should be recorded for future reference P701 Firmware Revision FIRMWARE X X N A Read Only Expert Level Menus 1 Touch the center of the Home screen 2 Press the Settings icon SCHEDULER displays 3 Press the left arrow 4 Press INSTALLER 5 Using the lower left and right arrows enter the password 6 Press PASSWORD to accept the password and return the unit ...

Page 13: ...in minutes before system will automatically switch from heating to cooling or vice versa P506 Cooling Deadband CL DEADBND 1 F 0 5 C to 5 F 4 0 C 1 F The deadband is divided equally above and below setpoint Cooling will begin when temperature exceeds upper point of deadband and ceases when temperature falls below lower point of deadband P507 Stage Delay Heating STG DLY HT 1 to 10 minutes 2 Time del...

Page 14: ...gized ON Relay energized P907 Test Output 1 OUT1 TST ON OFF OFF OFF Relay not energized ON Relay energized P908 Test Output 2 OUT2 TST ON OFF OFF OFF Relay not energized ON Relay energized P909 Test Output 3 OUT3 TST ON OFF OFF OFF Relay not energized ON Relay energized P911 Expert Password XPRT PW 50 00 to 99 99 99 99 Auxiliary Sequences The RDY2000 primary sequences are designed to control singl...

Page 15: ...ires a schedule to be configured Occupancy Notification Parameters P301 P305 P309 P313 If the optional occupancy sensor is used one of these must be set to 8 P317 P318 P319 To signal an external device that the space is occupied one of these must be set to 3 P404 If the optional occupancy sensor is used P404 can be used to set a minimum run timer for any actions that are activated by occupancy suc...

Page 16: ...y Evng Night Setpoint Heat F 70 62 70 62 70 68 70 62 70 68 70 62 Setpoint Cool F 75 82 75 82 75 78 75 82 75 78 75 82 Time 6 00 AM 10 00 PM 8 00 AM 10 00 PM 6 00 AM 11 00 AM 1 00 PM 10 00 PM 8 00 AM 11 00 AM 1 00 PM 10 00 PM Table 11 Work Week Schedule with Separate Weekend Days 2 Periods per Day Day Work Week Monday Friday Saturday Sunday Phase Day Night Day Night Day Night Setpoint Heat F 70 62 7...

Page 17: ...lass B digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee tha...

Page 18: ...erature Input 2 Type 0 P307 Temperature Input 2 Low 0 F 18 0 C P308 Temperature Input 2 High 120 F 50 0 C P309 Configurable Input 3 IN3 0 P310 Temperature Input 3 Type 0 P311 Temperature Input 3 Low 0 F 18 0 C P312 Temperature Input 3 High 120 F 50 0 C P313 Configurable Input 4 IN4 0 P314 Temperature Input 4 Type 0 P315 Temperature Input 4 Low 0 F 18 0 C P316 Temperature Input 4 High 120 F 50 0 C ...

Reviews: