72 / 88
For internal use only
Siemens
KNX bus communications
CE1P3127en
Building Technologies
Appendix
2013-04-08
Control strategy
Room control
combination
Effect
Same room
operating mode
Shared
setpoints
Slave external
setpoint
The slave ventilation controller shares
the same setpoint as the master:
Comfort heating setpoint
Pre-Comfort heating setpoint
Economy heating setpoint
The setpoints cannot be set in the
slave ventilation controllers. Any
setpoint adjustments required must be
made in the master ventilation
controller.
Same room
operating mode
Individual
setpoints
Slave internal
setpoint
The slave ventilation controller
operates with its own setpoints.
Room with floor heating and ventilation
Another application of the "Room control combination" is a room with floor heating
and a ventilation system. Exchanging the relevant process values over the KNX
bus allows for a common control strategy with the following aim:
Optimum control, heating or cooling.
The same room operating mode for both controllers
(time switch and holiday/special day program, manual override).
Automatische Umschaltung der Lüftungsregelung
(Winter:
Constant supply air temperature control, own setpoints).
(Summer:
Room/supply air cascade control).
M
M
T
p
p
T
M
M
p
T
T
T
M
3
1
2
7
S
0
2
2
2
Control strategy
Application example 3