background image

9 / 12 

Siemens 

PXC3.E...    Room automation stations 

CM1N9203en_05 

Building Technologies 

 

2015-11-23 

Assignment as per EN 

60730 

Operation of automatic controller 

Degree of pollution 

Construction type 

Type 1 

Protection class III 

Housing  

protection standard  

Protection type as per EN 60529 

Front parts in the DIN section 

Terminal part 

 

IP30 

IP20 

Ambient conditions 

Operation 

Climatic conditions 

 

Temperature           (see page 6) 

 

Humidity 

 

Mechanical conditions 

As per IEC 60721-3-3 

Class 3K5 

-5 ... 50 / 45 °C (23...122/113 °F)  

5…95% r.h.  

Class 3M2 

 

Transport 

Climatic conditions 

 

Temperature 

 

Humidity 

 

Mechanical conditions 

As per IEC 60721-3-2 

Class 2K3 

-25...70 °C (-13 ...158 °F) 

5…95% r.h.  

Class 2M2 

Standards, directives and 

approvals 

Product standard 

Product family standard 

General requirements for Home and 

Building Electronic Systems (HBES) and 

Building Automation and Control Systems 

(BACS) 

EN 60730-1 

 

EN 50491-2 

EN 50491-3  

EN 50491-5 

 

EU conformity (CE) 

See CM1T9203xx *)

 

 

Electromagnetic compatibility (EMC) 

For use in residential, commercial 

and industrial environments 

 

RCM-conformity (EMC) 

See CM1T9222en_C1 *) 

 

UL approbation 

UL 916  

 

EAC Eurasian conformity 

For all PXC3.E...-100A types 

 

Meets the requirements for eu.bac certification (excepted PXC3.E16A-100A). 

See product list on: 

http://www.eubaccert.org/licences-by-criteria.asp

 

License 

Application 

Control accuracy [K] 

212196 

Fan-Coil 4-pipe 

Heating / Cooling 

0.3 / 0.1 

 

 

 

Environmental 

compatibility 

The product environmental declaration 

CM1E9203 *) contains data on 

environmentally compatible product design 

and assessments (RoHS compliance, 

materials composition, packaging, 

environmental benefit, disposal) 

ISO 14001 (Environment) 

ISO 9001 (Quality) 

 

 

*)  The documents can be downloaded from 

http://siemens.com/bt/download

 

Color 

Housing 

RAL 7035 (light-gray) 

Dimensions 

Housing as per DIN 43 880, see dimensions 

 

Weight 

PXC3.E7x.... 

349g / 392g 

   Without / with 

packaging 

PXC3.E7xA... 

373g / 416g 

 

PXC3.E16A... 

347g / 390g 

Disposal 

 

The devices are considered electronics devices for disposal in terms of 

European Directive 2012/19/EU (WEEE) and may not be disposed of as 

domestic waste.  

Dispose of the devices via the proper channels.  

Follow all local and currently applicable laws and regulations. 

Summary of Contents for PXC3.E16A100A

Page 1: ...island bus to connect TX I O modules with any data point mix including bus supply Optional KNX PL Link peripheral bus to connect sensors actors and room units including bus supply Optional DALI bus to connect ballasts including bus supply Optional Connection of individual devices with KNX S Mode via KNX PL Link Ethernet switch for communication and tool connection USB Device interface Operating vo...

Page 2: ...gments 1 140 3 max 64 devices max 72 physical I O points max 64 ballasts 4 PXC3 E75 100A S55376 C132 typically 8 rooms typically 16 room segments 1 280 3 max 64 devices max 200 physical I O points PXC3 E75A 100A S55376 C133 typically 8 rooms typically 16 room segments 1 280 3 max 64 devices max 200 physical I O points max 64 ballasts 4 V5 1 V5 1SP 2 PXC3 E72 S55376 C100 typically 4 rooms typically...

Page 3: ...rcially available devices with KNX S Mode requires ETS engineering The DALI bus supports lighting control Commercially available DALI EBGs electronic ballasts can be connected Equipment combinations Depending on the type PXC3 series room automation stations can be operated with TX I O devices and devices with KNX PL Link DALI device type Description Supported 0 Fluorescent Lamps Yes 7 Switching Fu...

Page 4: ... bus supplies for island bus KNX PL Link and DALI are integrated in the room automation station For better reliability of the room automation station the bus supplies and the AC 24 V outlets are independent from the room automations station s own supply V6 The bus supplies are switched on by default and can be swiched off via tool if not needed V5 1 The bus supplies are switched off automatically ...

Page 5: ...X PL Link communication KNX PL Link not used or communication fault DALI Yellow Continuously ON Flashing Continuously OFF OK DALI bus communication DALI not used or communication fault SVC Red Continuously OFF Blinking Blinking per wink command OK No application loaded Physical identification of the room automation station Ether net 1 2 Green Continuously ON Continuously OFF Flashing Link active L...

Page 6: ...ed onto the mounting rail on the right side of the room automation station The island bus is created automatically in this process Recommended With restrictions Wall horizontal from left to right or from right to left Over head On a horizontal surface Wall vertical from bottom to top or from top to bottom Ambient temperature 5 50 C 23 122 F Ambient temperature 5 45 C 23 122 F 50 C 122 F is admissi...

Page 7: ...not used The NX PL Link supply MUST be switched off via tool if an external bus supply is used Transit power AC 24 V TX IO island bus KNX PL Link AC 24V terminals 3 4 AC 24 V 6 A terminals 7 and 8 for additional AC 24 V consumers 144 VA 6 A 48 VA 2 A 144 VA 6 A only if the sum of 10 A at terminals 5 and 6 is not exceeded Fusing of the supply outputs for field supply AC 24 V 2 A KNX PL Link termina...

Page 8: ... to 64 devices with KNX PL Link can be operated using one or two external bus supplies Protection Short circuit proof Protection against miswiring up to AC 24 V DALI interface Communications Interface type DALI galvanically separated Baud rate 1 2 kBit s Insulation strength Reinforced insulation for 230 V 1 5 kV Suitable for installations in overvoltage category III 4 kV Bus power supply Nominal v...

Page 9: ... residential commercial and industrial environments RCM conformity EMC See CM1T9222en_C1 UL approbation UL 916 EAC Eurasian conformity For all PXC3 E 100A types Meets the requirements for eu bac certification excepted PXC3 E16A 100A See product list on http www eubaccert org licences by criteria asp License Application Control accuracy K 212196 Fan Coil 4 pipe Heating Cooling 0 3 0 1 Environmental...

Page 10: ...t circuit proof with PTC resistor X X 8 24 V Operating voltage AC 24 V X X X 8 24 V 6 A Output AC 24 V to supply other PXC3 room automation stations internally connected to 24 V on pcb no internal fusing X X X F T 10 A fuse for island bus conductor V X X USB USB interface X X X 12 DALI DALI bus connection X X Service Service pin Ethernet X X X DALI DALI test X X Without labels Island bus The islan...

Page 11: ...en_05 Building Technologies 2015 11 23 24V CS 5 6 7 8 V 9203z05_01 T 10A 9 10 11 12 24V 24V 2A KNX 2 PTC KNX Island bus DALI DALI 3 1 2 3 4 Island Bus 1 1 2 Not with PXC3 E16A 100A 3 Only with PXC3 E A types Basic circuit diagram connections AC 24 V fusing ...

Page 12: ...12 12 Siemens PXC3 E Room automation stations CM1N9203en_05 Building Technologies 2015 11 23 Dimensions 9203M01 All dimensions in mm 2012 Siemens Switzerland Ltd Subject to change ...

Reviews: