Technical Instructions  

POWERS Controls 134-1861 Humidistat 

Document Number A6V11435226 
May 9, 2019 
 

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as 
design improvements are introduced. POWERS is a registered trademark of Siemens Industry, Inc. Other product or company names mentioned 
herein may be the trademarks of their respective owners. © 2019 Siemens Industry, Inc.

 

Siemens Industry, Inc. 

Smart Infrastructure 
1000 Deerfield Parkway 
Buffalo Grove, IL 60089 
+ 1 847-215-1000 

Your feedback is important to us. If you have comments about 
this document, please send them to 

[email protected]

 

Document No. 

A6V11435226

  

Printed in the USA 

Page 8 

 

 

Dial Lock, Continued 

4.  While holding the dial firmly in place, keep the setting in line with the calibrating 

mark, press Tab 

A

 and rotate it counterclockwise until it is against Stop Pin 

C

Press Tab 

B

 and rotate it clockwise until it is against Stop Pin 

C

. See Figure 7. 

5.  Ensure each tab fits into the notch closest to the stop. 

6.  Replace the humidistat cover, tighten the bottom cover screw, and replace the 

adjustment knob. 

Checkout Procedure 

Before applying power, ensure that installation and wiring connections are made 
according to job specifications. 

After all necessary adjustments and electrical connections have been made, put the 
system into operation and observe at least three complete operating cycles before 
leaving the installation. 

Service 

There is no servicing of the humidistat. For a replacement 134-1861, contact your local 
Siemens Industry representative. 

Dimensions 

 

Figure 8.  Dimensions of the 134-1861 Humidistat in Inches (Millimeters). 

 

 

Summary of Contents for POWERS 134-1861

Page 1: ...ion and dehumidification The differential of the 134 1861 is fixed at approximately 6 RH Features Human Hair Sensing Element Provides stable accurate measurement 1 4 HP 6A Rated Contacts Permit direct operation of many fans in commercial applications High low Adjustable Knob Range Stops Allow adjustments within a desired range Enclosed Pennswitch Provides dust protection for contacts Mounting Plat...

Page 2: ...or systems alarm supervisory systems that protect against or warn of control failure Operation The humidistat has a setpoint range of 0 to 70 RH as well as humidification off HUM OFF and dehumidification off DEH OFF positions At the HUM OFF position the C to L terminal circuit is open and the C to H terminal circuit is closed At the DEH OFF position the C to H terminal circuit is open and the C to...

Page 3: ...ed Cover Brown markings on goldanodized aluminum Mounting Vertical or horizontal 2 4 in 51 102 mm wall box Wiring terminals Large 8 32 1 4 in binder head screws Weight 0 9 lb 0 4 kg Dimensions 4 71 2 96 2 94 in 120 75 75 mm Agency listings UL Guide No XAPX File E6688 CSA Class No 4813 02 File LR948 Mounting and Installation General Guidelines Locate the 134 1861 as follows on an inside wall away f...

Page 4: ...ed Leave approximately 6 inches 152 mm of wire for connection to the humidistat terminals 3 Remove the humidistat mounting plate by loosening the mounting plate locking screw see Figure 1 and lifting and removing the plate from the base 4 Pull wires through the mounting plate and fasten the plate grounding screw end up to the wall box with the screws provided 5 Strip the wires and connect to the p...

Page 5: ...Position the horizontal faceplate over the factory installed vertical faceplate Ensure that the plate is positioned straight and even to over the existing plate 5 Firmly press the horizontal faceplate onto the humidistat cover 6 Replace the adjustment knob The installation is now complete Wiring Diagrams Figure 2 Typical Wiring Diagram of a 134 1861 Used to Reduce Excessive Humidity in a Well Cons...

Page 6: ...e following procedures to set the high and low range stops High Range Stop 1 Set the adjustment knob to the maximum desired RH setting 2 Pull the adjustment knob off the humidistat cover 3 Loosen the bottom cover screw and remove the humidistat cover CAUTION Equipment damage hazard Avoid contact with the human hair sensing element Contact with the hair element can affect control accuracy and or pr...

Page 7: ...see Figure 7 and rotate it clockwise until it is against the stop pin C 5 Release the tab making sure it fits into the nearest notch 6 Replace the humidistat cover tighten the bottom cover screw and replace the adjustment knob 7 Rotate adjustment knob to desired normal operating setpoint Figure 7 134 1861 Humidistat Range Tabs and Stop Dial Lock The high and low range stops can be set to keep the ...

Page 8: ... 8 Dial Lock Continued 4 While holding the dial firmly in place keep the setting in line with the calibrating mark press Tab A and rotate it counterclockwise until it is against Stop Pin C Press Tab B and rotate it clockwise until it is against Stop Pin C See Figure 7 5 Ensure each tab fits into the notch closest to the stop 6 Replace the humidistat cover tighten the bottom cover screw and replace...

Reviews: