background image

Technical Instructions  

POWERS Controls 134-1861 Humidistat 

Document Number A6V11435226 
May 9, 2019 

Page 2 

Siemens Industry, Inc.

 

 

Introduction 

The 134-1861 Humidistat provides SPDT control for use on low or line voltage 
applications. It has a thermoplastic cover with an Allen-head locking screw to discourage 
unauthorized tampering. The sensing element consists of carefully selected and 
processed human hair. 

An adjusting knob and easy-to-read dial allow quick selection of the desired setpoint. The 
humidistat is supplied with the faceplate installed for vertical mounting and knob 
adjustment. However, a horizontal faceplate is enclosed for horizontal mounting and 
knob adjustment if desired. There is also an optional Concealed Adjustment Faceplate 
(P/N 134-034) available for installations where humidity adjustment by the occupants is 
not desired. 

 

 

WARNING: 

The low temperature detection thermostat is designed for use only as an 
operating control. Where an operating control failure would result in 
personal injury and/or loss of property, it is the responsibility of the 
installer to add devices (safety, limit controls) or systems (alarm, 
supervisory systems) that protect against, or warn of control failure. 

Operation 

The humidistat has a setpoint range of 0 to 70% RH, as well as humidification off (

HUM 

OFF

) and dehumidification off (

DEH OFF

) positions. At the 

HUM OFF

 position, the C to L 

terminal circuit is open and the C to H terminal circuit is closed. At the 

DEH OFF

 position, 

the C to H terminal circuit is open and the C to L terminal controls the humidification 
equipment. 

At any given setpoint, the C to L circuit closes on a decrease in relative humidity, and the 
C to H circuit closes on an increase in relative humidity. 

The usual setting in winter is 30 to 40% RH. Lower settings may be necessary in 
extremely cold weather to prevent condensation on windows, doors, and so on. The 
same setting should be used where reduction of humidity by means of exhaust fans is 
provided in well-constructed homes. Summer settings on air conditioning or 
dehumidifying equipment will usually be near 50% RH. 

The suggested indoor humidity at 70

F (21

C) for residential applications on humidifying 

or dehumidifying equipment in winter is shown in Table 1. 

Table 1.  Humidity Settings. 

 

Outside Temperature 

Suggested Humidity Setting 

-20

F (-29

C) and Below

 

15% RH

 

-10

F (-23

C)

 

20% RH

 

0

F (-18

C)

 

25% RH

 

10

F (-12

C)

 

30% RH

 

20

F (-7

C)

 

35% RH

 

Above 20

F (-7

C)

 

40% RH or Higher as Desired

 

 

 

Summary of Contents for POWERS 134-1861

Page 1: ...ion and dehumidification The differential of the 134 1861 is fixed at approximately 6 RH Features Human Hair Sensing Element Provides stable accurate measurement 1 4 HP 6A Rated Contacts Permit direct operation of many fans in commercial applications High low Adjustable Knob Range Stops Allow adjustments within a desired range Enclosed Pennswitch Provides dust protection for contacts Mounting Plat...

Page 2: ...or systems alarm supervisory systems that protect against or warn of control failure Operation The humidistat has a setpoint range of 0 to 70 RH as well as humidification off HUM OFF and dehumidification off DEH OFF positions At the HUM OFF position the C to L terminal circuit is open and the C to H terminal circuit is closed At the DEH OFF position the C to H terminal circuit is open and the C to...

Page 3: ...ed Cover Brown markings on goldanodized aluminum Mounting Vertical or horizontal 2 4 in 51 102 mm wall box Wiring terminals Large 8 32 1 4 in binder head screws Weight 0 9 lb 0 4 kg Dimensions 4 71 2 96 2 94 in 120 75 75 mm Agency listings UL Guide No XAPX File E6688 CSA Class No 4813 02 File LR948 Mounting and Installation General Guidelines Locate the 134 1861 as follows on an inside wall away f...

Page 4: ...ed Leave approximately 6 inches 152 mm of wire for connection to the humidistat terminals 3 Remove the humidistat mounting plate by loosening the mounting plate locking screw see Figure 1 and lifting and removing the plate from the base 4 Pull wires through the mounting plate and fasten the plate grounding screw end up to the wall box with the screws provided 5 Strip the wires and connect to the p...

Page 5: ...Position the horizontal faceplate over the factory installed vertical faceplate Ensure that the plate is positioned straight and even to over the existing plate 5 Firmly press the horizontal faceplate onto the humidistat cover 6 Replace the adjustment knob The installation is now complete Wiring Diagrams Figure 2 Typical Wiring Diagram of a 134 1861 Used to Reduce Excessive Humidity in a Well Cons...

Page 6: ...e following procedures to set the high and low range stops High Range Stop 1 Set the adjustment knob to the maximum desired RH setting 2 Pull the adjustment knob off the humidistat cover 3 Loosen the bottom cover screw and remove the humidistat cover CAUTION Equipment damage hazard Avoid contact with the human hair sensing element Contact with the hair element can affect control accuracy and or pr...

Page 7: ...see Figure 7 and rotate it clockwise until it is against the stop pin C 5 Release the tab making sure it fits into the nearest notch 6 Replace the humidistat cover tighten the bottom cover screw and replace the adjustment knob 7 Rotate adjustment knob to desired normal operating setpoint Figure 7 134 1861 Humidistat Range Tabs and Stop Dial Lock The high and low range stops can be set to keep the ...

Page 8: ... 8 Dial Lock Continued 4 While holding the dial firmly in place keep the setting in line with the calibrating mark press Tab A and rotate it counterclockwise until it is against Stop Pin C Press Tab B and rotate it clockwise until it is against Stop Pin C See Figure 7 5 Ensure each tab fits into the notch closest to the stop 6 Replace the humidistat cover tighten the bottom cover screw and replace...

Reviews: