Siemens Polygyr-Compact Technical Instructions Download Page 4

Technical Instructions 

Polygyr-Compact Discharge Air Temperature Controller

Document Number CM1N3407E-P25
Rev. 1, February, 2000

Page 4 

Siemens Building Technologies, Inc.

Application

When the unit is switched off or the power supply interrupted (Terminal G), the
regulating unit is automatically run to the closed or no-load position.

A transformer is required to generate the operating voltage of 24 Vac. When several
units are connected, the size of the transformer is determined by adding up the power
consumption of the individual units. See 

Wiring Diagrams

 for connecting terminal

designations.

Every output of the RCM61.22 can control up to 10 units (actuators, converters, etc.) in
parallel operation. If a compensation input is used, attention must be paid to the input
signal.

Terminal Z1:

Input for universal compensation. The  5V ± 10V
corresponds to ± 100% of the theoretical setting range.

Terminal Z3:

Input for set point adjustment (fixed value shift). The 5V ±
5V corresponds to ± 10% of the theoretical setting range.

Mounting

Mounting location:

 

After the supply air fan, if the latte is mounted after the last air handling unit.

 

Otherwise, after the air handling unit, with a clearance of at least 1.64 feet.

The flexible sensing element should be positioned diagonally in the duct, but must not
come in contact with the duct wall.

Installation Instructions are supplied with the unit.

Commissioning

The wiring must be checked when commissioning the installation. To facilitate
commissioning, the controller can be operated as a P controller by using a service plug.

The correct operation of the regulating unit can be checked by setting the slider to its
limit positions. The factory-set P band Xp normally gives good control results. If
readjustment is required, the following must be noted:

 

In case of instability: Xp must be increased.

 

In case of excess stability: Xp must be decreased.

If auxiliary control functions (e.g., limitation, compensation) are fed to the controller, the
controlled value must first be adjusted, with no influence from the auxiliary control
functions. To do this, the terminals for auxiliary units must be disconnected. The
auxiliary values are adjusted only after the controlled value is adjusted.

If a remote setting unit is used, the slider for setting the desired temperature must be set
to “ext”.

Summary of Contents for Polygyr-Compact

Page 1: ...d cooling Application examples Individual installations kitchens cloak rooms storage rooms etc Zone control in larger installations The following units can be controlled Heating and cooling valve actuator Air damper actuator Step controller or current valve for electric air heater battery Signal converter The temperature controlled by the RCM61 22 can be shifted by the outdoor temperature to obtai...

Page 2: ...tes a control signal of 0 10 Vdc The outputs are switched in sequence and their mode of operation is opposed making it possible to provide sequence control of two actuators with different modes of operation Y Q Q Y Load Signal voltage Heating Cooling 0 10V SASC0016R1 0 Figure 1 Compensation The reference value is fed to the controller which shifts the set point There are two possibilities Universa...

Page 3: ...an be bent and adapted to the shape of the duct It senses the average temperature in the duct because the measuring element Ni wire extends over the total length of the flexible sensing element Unit Combinations The RCM61 22 can control various units with the following characteristics Type of control 10 Vdc Operating voltage 24 Vac Remote Setting Units The FZA21 11 remote setting unit is used for ...

Page 4: ...he supply air fan if the latte is mounted after the last air handling unit Otherwise after the air handling unit with a clearance of at least 1 64 feet The flexible sensing element should be positioned diagonally in the duct but must not come in contact with the duct wall Installation Instructions are supplied with the unit Commissioning The wiring must be checked when commissioning the installati...

Page 5: ...her switching functions which can vary from one installation to another according to the operating conditions SP SN 24V Y1 R M Z1 Z3 G Y1 G Y R M U G0 Y2 Y2 G Y R M U G0 N1 G0 SASC0018R1 R R1 M N1 RCM61 22 Discharge Air Temperature Controller R1 FZA21 11 Remote Setting Unit Y1 Actuator for heating Y2 Actuator for cooling Figure 3 Exhaust Air Temperature Control with Low Limiting of Discharge Air T...

Reviews: