Siemens Polygyr-Compact Technical Instructions Download Page 2

Technical Instructions 

Polygyr-Compact Discharge Air Temperature Controller

Document Number CM1N3407E-P25
Rev. 1, February, 2000

Page 2 

Siemens Building Technologies, Inc.

 

Function

The RCM61.22 provides PI control. The proportional band can be adjusted. The
controller compares the actual value with the set point and generates a proportional
control signal when a deviation occurs. The control signal is continuous and has a range
of 0 - 10 Vdc. When the control signal changes from 0 – 10 Vdc, the correcting variable
changes from 0 - 100%, i.e., there is a proportional relationship between the correcting
variable and the control signal. The adjusted Xp (proportional band) refers to heating
(Y1). The P band for cooling (Y2)is half as wide, making it possible to obtain the same
control quality for both heating and cooling, although the control conditions are different
(nearly the same plant gain with different correcting spans).

Each control output generates a control signal of 0 – 10 Vdc. The outputs are switched
in sequence and their mode of operation is opposed making it possible to provide
sequence control of two actuators with different modes of operation.

 

Y

Q

Q

Y

Load
Signal voltage
Heating
Cooling

0

10V

SASC0016R1

0

Figure 1.

 Compensation

The reference value is fed to the controller, which shifts the set point. There are two
possibilities:

 

Universal compensation over the whole setting range or over any part of the setting
range with the help of the RZF61.100 universal shift controller, or from a building
automation system.

 

Set point adjustment within ± 10% of the setting range; this is generally made from
a building automation system.

For more information on compensation, see 

Application

.

 

Design Features

The RCM61.22 is a small, electronic controller that combines electronics, setting scale
and sensing element into one unit.

The casing is plastic with a removable cover, fully active flexible sensing element, and
removable mounting flange with adjustable positions.

All setting devices and connecting terminals are contained in the housing and
accessible only when the cover is removed.

Summary of Contents for Polygyr-Compact

Page 1: ...d cooling Application examples Individual installations kitchens cloak rooms storage rooms etc Zone control in larger installations The following units can be controlled Heating and cooling valve actuator Air damper actuator Step controller or current valve for electric air heater battery Signal converter The temperature controlled by the RCM61 22 can be shifted by the outdoor temperature to obtai...

Page 2: ...tes a control signal of 0 10 Vdc The outputs are switched in sequence and their mode of operation is opposed making it possible to provide sequence control of two actuators with different modes of operation Y Q Q Y Load Signal voltage Heating Cooling 0 10V SASC0016R1 0 Figure 1 Compensation The reference value is fed to the controller which shifts the set point There are two possibilities Universa...

Page 3: ...an be bent and adapted to the shape of the duct It senses the average temperature in the duct because the measuring element Ni wire extends over the total length of the flexible sensing element Unit Combinations The RCM61 22 can control various units with the following characteristics Type of control 10 Vdc Operating voltage 24 Vac Remote Setting Units The FZA21 11 remote setting unit is used for ...

Page 4: ...he supply air fan if the latte is mounted after the last air handling unit Otherwise after the air handling unit with a clearance of at least 1 64 feet The flexible sensing element should be positioned diagonally in the duct but must not come in contact with the duct wall Installation Instructions are supplied with the unit Commissioning The wiring must be checked when commissioning the installati...

Page 5: ...her switching functions which can vary from one installation to another according to the operating conditions SP SN 24V Y1 R M Z1 Z3 G Y1 G Y R M U G0 Y2 Y2 G Y R M U G0 N1 G0 SASC0018R1 R R1 M N1 RCM61 22 Discharge Air Temperature Controller R1 FZA21 11 Remote Setting Unit Y1 Actuator for heating Y2 Actuator for cooling Figure 3 Exhaust Air Temperature Control with Low Limiting of Discharge Air T...

Reviews: