Polygyr-Compact Discharge Air Temperature Controller

Technical Instructions

Document Number CM1N3407E-P25

Rev. 1, February, 2000

Siemens Building Technologies, Inc.

Page 3

 

Design Features,
Continued

1 Connecting

terminals

2 Setting

potentiometer for
P band

3 Slider for setting

the desired value

4 Setting scale

5 Service plug

6 Mounting flange

7 Flexible sensing

element

 

Figure 2.

 

The scale and slider for setting the desired temperature can be seen through a window
in the cover. Knock-out holes (Pg11) provide entry for the cables.

After fitting the mounting flange to the duct wall, the controller can be installed in seven
different positions so that, with layers of insulation up to 2.76 inches, the controller
housing will not be insulated.

The detector can be bent and adapted to the shape of the duct. It senses the average
temperature in the duct because the measuring element (Ni wire) extends over the total
length of the flexible sensing element.

 

Unit Combinations

The RCM61.22 can control various units with the following characteristics:

 

Type of control

10 Vdc

 Operating 

voltage

24 

Vac

 Remote Setting Units

The FZA21.11 remote setting unit is used for remote setting of the desired value.

 

Specifications

 

Operating voltage

24 Vac ± 20%

Frequency

50 – 60 Hz

Power consumption

1 VA

Control signal:

Voltage

0 – 10 Vdc, continuous

Current

1 mA

Integral action time

2 minutes

Measuring element

LG-Ni 1000 

 @ 32°F (0°C)

Time constant

30 seconds at 6.5 ft/s

Setting ranges

Set point

32 – 122°F (0 – 50°C)

Proportional band Xp

4 – 100 % 3.6 - 90°F

Permissible ambient temperature:

Operation

14 – 122°F (-10 – 50°C)

Transport and storage

-13 – 149°F (-25 – 65°C)

Cable entry fitting

Pg11

Connecting terminals

for 2 x 14 AWG or 1 x 12 AWG

Weight

0.55 lb.

Summary of Contents for Polygyr-Compact

Page 1: ...d cooling Application examples Individual installations kitchens cloak rooms storage rooms etc Zone control in larger installations The following units can be controlled Heating and cooling valve actuator Air damper actuator Step controller or current valve for electric air heater battery Signal converter The temperature controlled by the RCM61 22 can be shifted by the outdoor temperature to obtai...

Page 2: ...tes a control signal of 0 10 Vdc The outputs are switched in sequence and their mode of operation is opposed making it possible to provide sequence control of two actuators with different modes of operation Y Q Q Y Load Signal voltage Heating Cooling 0 10V SASC0016R1 0 Figure 1 Compensation The reference value is fed to the controller which shifts the set point There are two possibilities Universa...

Page 3: ...an be bent and adapted to the shape of the duct It senses the average temperature in the duct because the measuring element Ni wire extends over the total length of the flexible sensing element Unit Combinations The RCM61 22 can control various units with the following characteristics Type of control 10 Vdc Operating voltage 24 Vac Remote Setting Units The FZA21 11 remote setting unit is used for ...

Page 4: ...he supply air fan if the latte is mounted after the last air handling unit Otherwise after the air handling unit with a clearance of at least 1 64 feet The flexible sensing element should be positioned diagonally in the duct but must not come in contact with the duct wall Installation Instructions are supplied with the unit Commissioning The wiring must be checked when commissioning the installati...

Page 5: ...her switching functions which can vary from one installation to another according to the operating conditions SP SN 24V Y1 R M Z1 Z3 G Y1 G Y R M U G0 Y2 Y2 G Y R M U G0 N1 G0 SASC0018R1 R R1 M N1 RCM61 22 Discharge Air Temperature Controller R1 FZA21 11 Remote Setting Unit Y1 Actuator for heating Y2 Actuator for cooling Figure 3 Exhaust Air Temperature Control with Low Limiting of Discharge Air T...

Reviews: