OP1S Operator Control Panel
Siemens AG
477 459 4070 72 J AA-6R
SIMOVERT MASTERDRIVES
Operating Instructions
1
1 General
The operator control panel (OP1S) is an optional input/output device which can be used
for parameterizing and starting up the units. Plain-text displays greatly facilitate
parameterization.
The OP1S has a non-volatile memory and can permanently store complete sets of
parameters. It can therefore be used for archiving sets of parameters but, first, the
parameter sets must be read out (upread) from the units. Stored parameter sets can also
be transferred (downloaded) to other units.
The OP1S and the units to be operated communicate with each other via a serial
interface (RS485) using the USS protocol. During communication, the OP1S assumes
the function of a master whereas the connected units function as slaves.
The OP1S can be operated at baud rates of 9.6 kBd and 19.2 kBd and is capable of
communicating with up to 32 slaves (addresses 0 to 31). It can therefore be used in a
point-to-point link (e.g. during initial parameterization) or within a bus configuration.
The plain-text displays can be shown in one of five different languages (German, English,
Spanish, French, Italian). The language is chosen by selecting the relevant parameter for
the slave in question.
Order numbers
Components
Order No.
OP1S
6SE7090-0XX84-2FK0
Connecting cable 3 m
6SX7010-0AB03
Connecting cable 5 m
6SX7010-0AB05
Adapter for installation in cabinet door, incl. 5 m cable
6SX7010-0AA00
NOTE
The parameter settings for units connected to the OP1S are given in the
corresponding documentation (Compendium).