Information in this document is based on specifications believed correct at the time of publication. The right is
reserved to make changes as design improvements are introduced. Product or company names mentioned herein
may be the trademarks of their respective owners.
© 2019 Siemens Industry, Inc.
Siemens Industry, Inc
.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
USA
+1-847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them
Document No. A6V11564207
Printed in the USA
Page 73
Communication Rate
(baud)
9600 (Default), 19200, 38400, 57600, 76800, 115200
Data Bits
8
Parity
None, Even, Odd
Stop Bit
2, 1
Termination
None provided
Data Formats
Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP
Mechanical
Wire Connections
12-22 AWG 600 Vac, Voltage connection must be #14 AWG or larger & 600 VAC
rated
Mounting
Enclosure or Panel Mount
High Voltage Cover
IP30. Available with MD-48HD/MD-12HD Enclosure and MD-48HD Plate models
Operating Temperature
-20 to + 60
⁰
C (-4 to 140
⁰
F) (the colder the temperature the more voltage is
needed to power the board)
Humidity
5% to 95% non-condensing
Enclosure
ABS Plastic, 94-V0 flammability rating, connections sized for 1
–inch EMT conduit
MD-48HD Dimensions
(L) 33.7cm × (W) 25.1cm ×
(H) 8.0 cm (13.3” × 9.8” × 3.1”) (enclosure version)
(L) 26.2cm × (W) 24.1cm ×
(H) 8.0 cm (10.3” × 9.5” × 3.1”) (mounting plate
version)
MD-12HD Dimensions
(L) 24.8cm × (W) 25.1cm × (H) 8.0
cm (9.8” × 9.8” × 3.1”) (enclosure version)
(L) 17.8cm × (W) 26.3cm ×
(H) 8.0 cm (7.0” × 10.4” × 3.1”) (mounting plate
version)
PCBA Dimensions
(L) 21.6cm × (W) 21.6cm ×
(H) 6.4 cm (8.5” × 8.5” × 2.5”)
ViewPoint
™ HD Minimum System Requirements
Operating System
Windows® 7, Windows® 8, Windows® 10
Communications Port
USB or Ethernet connectivity
Safety
FCC Compliance
This device has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at
user’s own expense.
Serial/Ethernet Meters
The following are UL Recognized:
MD-12HD-P-y-z, MD-48HD-P-y-z
The following are UL Listed:
MD12HD-C-y-z , MD-48HD-C-y-z
Conforms to UL Std 61010-1, 3rd Edition, UL 61010-2-30:2010
Certified to CSA Std C22.2 No. 61010-1, 3rd Edition
Summary of Contents for MD-12HD
Page 1: ...ii Siemens Industry Inc User Guide MD 12HD MD 48HD Networked Metering Systems A6V11564207 ...
Page 2: ......
Page 27: ...Siemens Industry inc 26 Configuring Electrical Components using ViewPoint HD ...
Page 68: ...67 Siemens Industry Inc Menu Navigation ...
Page 69: ...Siemens Industry inc 68 Communication Navigation ...