Power Factor Convention
Power Factor is the ratio of a signed number (true power) and an unsigned number (apparent power).
This discrepancy has led to some customer confusion. The MD-xxHD meter allows users to select
between two conventions (ANSI and IEEE). In the IEEE convention the sign of
PF
follows the sign of
power itself. In the ANSI convention a “+” PF indicates a lagging current (inductive load) while a “–“ PF
indicates a leading current (capacitive load). The sign relationships are shown below for these
conventions in each electrical quadrant.
Total Harmonic Distortion
The MD-xxHD meter reports overall harmonic content in power (% THD) based on its measurement of
Power, Var and Apparent Power as illustrated in the figure below. This method cannot indicate the
harmonic number or distribution but provides the overall harmonic content.
In many circumstances users are interested in the harmonic content of
current
. In cases where the
voltage is very sinusoidial the THD measurement is a good estimate of both power and current.
However, if the voltage waveform is distorted the reported THD in power can be misleading. ViewPoint
HD can provide additional analysis of harmonic content in voltage and current by sampling the MD-xxHD
raw data and performing digital signal processing on the signal. Using this method the individual
harmonics levels can be observed. The results are presented in graphical form.
Summary of Contents for MD-12HD
Page 1: ...ii Siemens Industry Inc User Guide MD 12HD MD 48HD Networked Metering Systems A6V11564207 ...
Page 2: ......
Page 27: ...Siemens Industry inc 26 Configuring Electrical Components using ViewPoint HD ...
Page 68: ...67 Siemens Industry Inc Menu Navigation ...
Page 69: ...Siemens Industry inc 68 Communication Navigation ...