Nominal size
Cable gland for Ex e II
Type HSK-M
Cable gland for Ex e / Ex d IIC
Type ADE 1F, ADE 4F R... / B...
Union nut
Connection thread
Union nut / connection
thread
Union nut / connection
thread
M20 x 1.5
5
7
20
23
M25 x 1.5
7
10
30
29
M32 x 1.5
7
10
55
33
M40 x 1.5
7
10
75
41
M50 x 1.5
7
10
100
50
M63 x 1.5
7
10
135
75
M75 x 1.5
-
-
175
100
6.2.11
Connecting aluminum conductors
If you are using aluminum conductors, comply in addition with the following:
● Use only cable lugs that are suitable for connecting aluminum conductors.
● Immediately before inserting the aluminum conductor, remove the oxide layer from the
contact areas on the conductor and/or the mating piece, by brushing or filing.
● Then grease the contact areas immediately using neutral vaseline in order to avoid re-
oxidation.
NOTICE
Aluminum flow due to contact pressure
Aluminum flows following installation due to the contact pressure. The connection with the
clamping nuts can loosen as a result. The contact resistance would increase and the
current-carrying impeded; as a consequence the terminal box and the surrounding
components could burn. This could result in material damage to the machine or even in
total failure, which could in turn lead to indirect material damage to the system.
Retighten the clamping nuts after approximately 24 hours and then again after
approximately four weeks. Make sure that the terminals are de-energized before you
tighten the nuts.
6.2.12
O-ring seal
If O-ring seals are present, you should check that they are in perfect condition and that the O-
ring seals are properly seated in the grooves between the components. Replace any damaged
O-ring seals.
O-ring seals can be present on the following components, for instance:
● Tapers
● Cable glands
● Bearing seals
Electrical connection
6.2 Connecting
LOHER CHEMSTAR 1PS2
Operating Instructions 08/2016
61
Summary of Contents for LOHER CHEMSTAR 1PS2
Page 2: ...04 08 2016 11 45 V3 00 ...
Page 64: ...Electrical connection 6 2 Connecting LOHER CHEMSTAR 1PS2 64 Operating Instructions 08 2016 ...
Page 74: ...Start up 7 8 Test run LOHER CHEMSTAR 1PS2 74 Operating Instructions 08 2016 ...
Page 84: ...Operation 8 11 faults LOHER CHEMSTAR 1PS2 84 Operating Instructions 08 2016 ...
Page 102: ...Maintenance 9 2 Corrective Maintenance LOHER CHEMSTAR 1PS2 102 Operating Instructions 08 2016 ...
Page 118: ...Service and Support LOHER CHEMSTAR 1PS2 118 Operating Instructions 08 2016 ...
Page 120: ...Technical data and drawings LOHER CHEMSTAR 1PS2 120 Operating Instructions 08 2016 ...
Page 142: ...Index LOHER CHEMSTAR 1PS2 142 Operating Instructions 08 2016 ...