Configuring and commissioning using ETS
8.6 Transfer of data from LOGO! to KNX
CMK2000
Operating Instructions, 11/2015, A5E34877550B/001
65
8.6.6
Transferring integer values
Image 8-15 Data transfer LOGO! to KNX: Integer values
LOGO! data type / KNX data type
LOGO! data type
KNX data type
Analog input
•
2 bytes unsigned - DPT 7.xxx (default)
•
2 bytes signed - DPT 8.xxx
Analog output
Analog flag
1-byte variable memory
•
1 byte unsigned - DPT 5.010
•
1 byte signed - DPT 6.010
2-byte variable memory
•
2 bytes unsigned - DPT 7.xxx (default)
•
2 bytes signed - DPT 8.xxx
4-byte variable memory
•
4 bytes unsigned - DPT 12.xxx (default)
•
4 bytes signed - DPT 13.xxx
See also
Value update with data transfer from LOGO! to KNX (Page 47)
Response after startup of LOGO!, CMK2000 or KNX (Page 51)