Configuring and commissioning using ETS
8.5 Parameter assignments for the KNX channels
CMK2000
48
Operating Instructions, 11/2015, A5E34877550B/001
8.5.5
Value scaling of the channels
LOGO! and KNX work internally with different ranges of values. Therefore scaling is required
for transferring certain data types between KNX and LOGO!. Linear scaling can be
parameterized using two interpolation points.
Parameter assignment
Transfer from LOGO! to KNX
Transfer from KNX to LOGO!
Linear scaling can be parameterized for the following linked objects.
Transfer between LOGO! and KNX
KNX data type
Range of values for
scaling
on the KNX bus
LOGO! data type
Range of values for
scaling in the
LOGO!
1 byte 0...100% DPT 5.001
0 … 255
1-byte variable
memory
0 … 255
2-byte float value - DPT 9.xxx -671088.64 …
670760.96
2-byte variable
memory
-32768 … 32767