12 Parameter list / legend of parameter bit fields LMU...
07.11.2002
KonfigRg5
Setting flags
H2Oueb
Water shortage switch (input X11-3)
XXXX XX00
flow switch -> lockout
XXXX XX01
flow switch -> start prevention
XXXX XX10
pressure switch -> lockout
XXXX XX11
pressure switch -> start prevention
DrehBegr
Speed limitation
XXXX X0XX
OFF
XXXX X1XX
ON
H2OUebSens
Water pressure supervision with pressure sensor
XXX0 0XXX
deactivated
XXX0 1XXX
activated with start prevention
XXX1 0XXX
activated with lockout
AbgasUeb
Flue gas temperature supervision
X00X XXXX
deactivated
X01X XXXX
activated with start prevention
X10X XXXX
activated with lockout
H2OUmlauf
Water flow supervision with pressure sensor
0XXX XXXX
error leads to start prevention
1XXX XXXX
error leads to a lockout position
KonfigRg6
Setting flags
PIDinit
XXXX XXX0
internal
KundenRU
Locking RU of other manufacture
XXXX XX0X
OFF
XXXX XX1X
ON
BwSoll
Source of DHW setpoint
XXXX X0XX
RU (if connected)
XXXX X1XX
MMI (also when a RU is connected)
Sperrsignal
Calculation of locking signal
XXXX 0XXX
calculation of locking signal deactivated
XXXX 1XXX
calculation of locking signal active
ReglStopSave
Output can be stored at end of controller stop function
XXX0 XXXX
output cannot be stored
XXX1 XXXX
output can be stored
DrehGrWechsel
Activation of fast speed limit changes
XX0 X XXXX
normal handling
XX1 X XXXX
accelerated handling of fast changes
KonfigRg7
Setting flags
ModQ1
Heating circuit pump
XXXX XXX0
multispeed
XXXX XXX1
modulating
DtBegr
dt limitation
XXXX XX0X
OFF
XXXX XX1X
ON
DtRegelung
dt control
XXXX X0XX
OFF
XXXX X1XX
ON