![Siemens LMU54 Series Basic Documentation Download Page 127](http://html.mh-extra.com/html/siemens/lmu54-series/lmu54-series_basic-documentation_377199127.webp)
127/171
Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
10 Technical data
07.11.2002
10.2 Clip-in
10.2.1 AGU2.500...
Mixing circuit pump and mixing valve
- Voltage
AC 230 V +10 % -15 %
- Current
5 mA ... 1 A, cos
ϕ >
0.8
When assigning loads to the outputs, the
total current draw
of the LMU… system must
be taken into consideration!
Flow sensor NTC 10 k
Ω
like boiler sensor
10.2.2 AGU2.51x
Up to 3 outputs (K1...K3)
When using 2 clip-in modules with the LMU…, only 2 outputs possible
- Voltage
AC 230 V +10 % -15 %
- Current
5 mA ... 1 A, cos
ϕ >
0.8
When assigning loads to outputs K1...K3, the
total
current draw of the LMU… system
must be taken into consideration!
Version
Input
Remarks
AGU2.511A109
0...10 V
Note polarity
AGU2.513A109
(0)4...20 mA
Note polarity
AGU2.514A109
NTC 10 k
Ω
Like boiler sensor
AGU2.515A109
1)
1) Contact rating: Nom. DC 34 V / 5 mA
The inputs may only be used with safety extra low-voltage (SELV) and may not be
connected to protective earth (PE)!
Outputs
Electrical connections
Note
Input
Outputs
Electrical connections
Note
Input
Note