143/171
Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
12 Parameter list / legend of parameter bit fields LMU...
07.11.2002
KonfigRg2
Instantaneous DHW heater setting flags
DlhNachlInBw
Pump overrun into the heating circuit or into the inst. DHW
heat exchanger
XXXX XXX0
overrun into the heating circuit
XXXX XXX1
overrun into the inst. DHW heat exchanger
DlhKomfTemp
Definition of comfort temperature level
XXXX XX0X
same level as outlet temperature
XXXX XX1X
parameter
«
TbwBereit
DlhKomfReglF Comfort PID control sensor
XXXX 00XX
boiler sensor (flow)
XXXX 01XX
DHW1 sensor (abortion criterion: time)
XXXX 10XX
return sensor (B7)
KonfigRg3
AD converter and HC demand
ADkon0
Configuration AD converter inputs
XXX0 0001
configuration 1
XXX0 0010
configuration 2
XXX0 0011
configuration 3
XXX0 0100
configuration 4
Hz1set
Heat demand 1
XX0X XXXX
internal
Hz2set
Heat demand 2
X0XX XXXX
internal
HzZoSet
Heat demand zone
0XXX XXXX
internal
KonfigRg4
Setting flags
Q8Fkt
System function
XXXX XXX0
OFF
XXXX XXX1
ON
GebBauweise
Type of building construction
XXXX XX0X
light
XXXX XX1X
heavy
Bw-Thermostat Selection of terminals on DHW thermostat
XXXX X0XX
DHW thermostat connected to X11 (digital
input)
XXXX X1XX
DHW thermostat connected to X10-05
(analog input)
H2OUmlaufVor Location of water pressure sensor in relation to the pump
XXXX 0XXX
pressure increase due to pump on
XXXX 1XXX
pressure decrease due to pump on
K2aufUV
Transfer of basic function from K2 to K3 (only with stepper
motor diverting valve)
XXX0 XXXX
default (K3 unchanged)
XXX1 XXXX
transfer of basic function from K2 to K3,
UvKon
Configuration of diverting valve
000X XXXX
no diverting valve
001X XXXX
magnetic valve (0 = HC; 1 = DHW)
010X XXXX
motorized valve (0 = HC; 1 = DHW)
011X XXXX
mototized valve (1 = HC; 0 = DHW)
100X XXXX
stepper motor valve, unipolar
101X XXXX
stepper motor valve, bipolar